cimpy.cgmes_v2_4_15.WindContCurrLimIEC module
- class cimpy.cgmes_v2_4_15.WindContCurrLimIEC.WindContCurrLimIEC(WindDynamicsLookupTable='list', WindTurbineType3or4IEC=None, imax=0.0, imaxdip=0.0, mdfslim=False, mqpri=False, tufilt=0.0, *args, **kw_args)[source]
Current limitation model. The current limitation model combines the physical limits. Reference: IEC Standard 61400-27-1 Section 6.6.5.7.
- WindDynamicsLookupTable:
The current control limitation model with which this wind dynamics lookup table is associated. Default: “list”
- WindTurbineType3or4IEC:
Wind turbine type 3 or 4 model with which this wind control current limitation model is associated. Default: None
- imax:
Maximum continuous current at the wind turbine terminals (). It is type dependent parameter. Default: 0.0
- imaxdip:
Maximum current during voltage dip at the wind turbine terminals (). It is project dependent parameter. Default: 0.0
- mdfslim:
Limitation of type 3 stator current (): - false=0: total current limitation, - true=1: stator current limitation). It is type dependent parameter. Default: False
- mqpri:
Prioritisation of q control during LVRT (): - true = 1: reactive power priority, - false = 0: active power priority. It is project dependent parameter. Default: False
- tufilt:
Voltage measurement filter time constant (). It is type dependent parameter. Default: 0.0
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’