cimpy.cgmes_v2_4_15.GovSteam1 module
- class cimpy.cgmes_v2_4_15.GovSteam1.GovSteam1(db1=0.0, db2=0.0, eps=0.0, gv1=0.0, gv2=0.0, gv3=0.0, gv4=0.0, gv5=0.0, gv6=0.0, k=0.0, k1=0.0, k2=0.0, k3=0.0, k4=0.0, k5=0.0, k6=0.0, k7=0.0, k8=0.0, mwbase=0.0, pgv1=0.0, pgv2=0.0, pgv3=0.0, pgv4=0.0, pgv5=0.0, pgv6=0.0, pmax=0.0, pmin=0.0, sdb1=False, sdb2=False, t1=0.0, t2=0.0, t3=0.0, t4=0.0, t5=0.0, t6=0.0, t7=0.0, uc=0.0, uo=0.0, valve=False, *args, **kw_args)[source]
Steam turbine governor model, based on the GovSteamIEEE1 model (with optional deadband and nonlinear valve gain added).
- db1:
Intentional deadband width (db1). Unit = Hz. Typical Value = 0. Default: 0.0
- db2:
Unintentional deadband (db2). Unit = MW. Typical Value = 0. Default: 0.0
- eps:
Intentional db hysteresis (eps). Unit = Hz. Typical Value = 0. Default: 0.0
- gv1:
Nonlinear gain valve position point 1 (GV1). Typical Value = 0. Default: 0.0
- gv2:
Nonlinear gain valve position point 2 (GV2). Typical Value = 0.4. Default: 0.0
- gv3:
Nonlinear gain valve position point 3 (GV3). Typical Value = 0.5. Default: 0.0
- gv4:
Nonlinear gain valve position point 4 (GV4). Typical Value = 0.6. Default: 0.0
- gv5:
Nonlinear gain valve position point 5 (GV5). Typical Value = 1. Default: 0.0
- gv6:
Nonlinear gain valve position point 6 (GV6). Typical Value = 0. Default: 0.0
- k:
Governor gain (reciprocal of droop) (K) (>0). Typical Value = 25. Default: 0.0
- k1:
Fraction of HP shaft power after first boiler pass (K1). Typical Value = 0.2. Default: 0.0
- k2:
Fraction of LP shaft power after first boiler pass (K2). Typical Value = 0. Default: 0.0
- k3:
Fraction of HP shaft power after second boiler pass (K3). Typical Value = 0.3. Default: 0.0
- k4:
Fraction of LP shaft power after second boiler pass (K4). Typical Value = 0. Default: 0.0
- k5:
Fraction of HP shaft power after third boiler pass (K5). Typical Value = 0.5. Default: 0.0
- k6:
Fraction of LP shaft power after third boiler pass (K6). Typical Value = 0. Default: 0.0
- k7:
Fraction of HP shaft power after fourth boiler pass (K7). Typical Value = 0. Default: 0.0
- k8:
Fraction of LP shaft power after fourth boiler pass (K8). Typical Value = 0. Default: 0.0
- mwbase:
Base for power values (MWbase) (>0). Unit = MW. Default: 0.0
- pgv1:
Nonlinear gain power value point 1 (Pgv1). Typical Value = 0. Default: 0.0
- pgv2:
Nonlinear gain power value point 2 (Pgv2). Typical Value = 0.75. Default: 0.0
- pgv3:
Nonlinear gain power value point 3 (Pgv3). Typical Value = 0.91. Default: 0.0
- pgv4:
Nonlinear gain power value point 4 (Pgv4). Typical Value = 0.98. Default: 0.0
- pgv5:
Nonlinear gain power value point 5 (Pgv5). Typical Value = 1. Default: 0.0
- pgv6:
Nonlinear gain power value point 6 (Pgv6). Typical Value = 0. Default: 0.0
- pmax:
Maximum valve opening (Pmax) (> Pmin). Typical Value = 1. Default: 0.0
- pmin:
Minimum valve opening (Pmin) (>=0). Typical Value = 0. Default: 0.0
- sdb1:
Intentional deadband indicator. true = intentional deadband is applied false = intentional deadband is not applied. Typical Value = true. Default: False
- sdb2:
Unintentional deadband location. true = intentional deadband is applied before point A false = intentional deadband is applied after point A. Typical Value = true. Default: False
- t1:
Governor lag time constant (T1). Typical Value = 0. Default: 0.0
- t2:
Governor lead time constant (T2). Typical Value = 0. Default: 0.0
- t3:
Valve positioner time constant (T3(>0). Typical Value = 0.1. Default: 0.0
- t4:
Inlet piping/steam bowl time constant (T4). Typical Value = 0.3. Default: 0.0
- t5:
Time constant of second boiler pass (T5). Typical Value = 5. Default: 0.0
- t6:
Time constant of third boiler pass (T6). Typical Value = 0.5. Default: 0.0
- t7:
Time constant of fourth boiler pass (T7). Typical Value = 0. Default: 0.0
- uc:
Maximum valve closing velocity (Uc) (<0). Unit = PU/sec. Typical Value = -10. Default: 0.0
- uo:
Maximum valve opening velocity (Uo) (>0). Unit = PU/sec. Typical Value = 1. Default: 0.0
- valve:
Nonlinear valve characteristic. true = nonlinear valve characteristic is used false = nonlinear valve characteristic is not used. Typical Value = true. Default: False
Documentation of parent class TurbineGovernorDynamics:
Turbine-governor function block whose behavior is described by reference to a standard model
- AsynchronousMachineDynamics:
Asynchronous machine model with which this turbine-governor model is associated. Default: None
- SynchronousMachineDynamics:
Turbine-governor model associated with this synchronous machine model. Default: “list”
- TurbineLoadControllerDynamics:
Turbine load controller providing input to this turbine-governor. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’