- class cimpy.cgmes_v2_4_15.ExcAVR3.ExcAVR3(e1=0.0, e2=0.0, ka=0.0, se1=0.0, se2=0.0, t1=0.0, t2=0.0, t3=0.0, t4=0.0, te=0.0, vrmn=0.0, vrmx=0.0, *args, **kw_args)[source]
Italian excitation system. It represents exciter dynamo and electric regulator.
- e1:
Field voltage value 1 (E1). Typical Value = 4.18. Default: 0.0
- e2:
Field voltage value 2 (E2). Typical Value = 3.14. Default: 0.0
- ka:
AVR gain (K). Typical Value = 3000. Default: 0.0
- se1:
Saturation factor at E1 (S(E1)). Typical Value = 0.1. Default: 0.0
- se2:
Saturation factor at E2 (S(E2)). Typical Value = 0.03. Default: 0.0
- t1:
AVR time constant (T). Typical Value = 220. Default: 0.0
- t2:
AVR time constant (T). Typical Value = 1.6. Default: 0.0
- t3:
AVR time constant (T). Typical Value = 0.66. Default: 0.0
- t4:
AVR time constant (T). Typical Value = 0.07. Default: 0.0
- te:
Exciter time constant (T). Typical Value = 1. Default: 0.0
- vrmn:
Maximum AVR output (V). Typical Value = -7.5. Default: 0.0
- vrmx:
Minimum AVR output (V). Typical Value = 7.5. Default: 0.0
Documentation of parent class ExcitationSystemDynamics:
Excitation system function block whose behavior is described by reference to a standard model
- DiscontinuousExcitationControlDynamics:
Discontinuous excitation control model associated with this excitation system model. Default: None
- OverexcitationLimiterDynamics:
Overexcitation limiter model associated with this excitation system model. Default: None
- PFVArControllerType1Dynamics:
Power Factor or VAr controller Type I model associated with this excitation system model. Default: None
- PFVArControllerType2Dynamics:
Power Factor or VAr controller Type II model associated with this excitation system model. Default: None
- PowerSystemStabilizerDynamics:
Power system stabilizer model associated with this excitation system model. Default: None
- SynchronousMachineDynamics:
Synchronous machine model with which this excitation system model is associated. Default: None
- UnderexcitationLimiterDynamics:
Undrexcitation limiter model associated with this excitation system model. Default: None
- VoltageCompensatorDynamics:
Voltage compensator model associated with this excitation system model. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’