class cimpy.cgmes_v2_4_15.GovHydroWPID.GovHydroWPID(d=0.0, gatmax=0.0, gatmin=0.0, gv1=0.0, gv2=0.0, gv3=0.0, kd=0.0, ki=0.0, kp=0.0, mwbase=0.0, pgv1=0.0, pgv2=0.0, pgv3=0.0, pmax=0.0, pmin=0.0, reg=0.0, ta=0.0, tb=0.0, treg=0.0, tw=0.0, velmax=0.0, velmin=0.0, *args, **kw_args)[source]

Woodward PID Hydro Governor.

d:

Turbine damping factor (D). Unit = delta P / delta speed. Default: 0.0

gatmax:

Gate opening Limit Maximum (Gatmax). Default: 0.0

gatmin:

Gate opening Limit Minimum (Gatmin). Default: 0.0

gv1:

Gate position 1 (Gv1). Default: 0.0

gv2:

Gate position 2 (Gv2). Default: 0.0

gv3:

Gate position 3 (Gv3). Default: 0.0

kd:

Derivative gain (Kd). Typical Value = 1.11. Default: 0.0

ki:

Reset gain (Ki). Typical Value = 0.36. Default: 0.0

kp:

Proportional gain (Kp). Typical Value = 0.1. Default: 0.0

mwbase:

Base for power values (MWbase) (>0). Unit = MW. Default: 0.0

pgv1:

Output at Gv1 PU of MWbase (Pgv1). Default: 0.0

pgv2:

Output at Gv2 PU of MWbase (Pgv2). Default: 0.0

pgv3:

Output at Gv3 PU of MWbase (Pgv3). Default: 0.0

pmax:

Maximum Power Output (Pmax). Default: 0.0

pmin:

Minimum Power Output (Pmin). Default: 0.0

reg:

Permanent drop (Reg). Default: 0.0

ta:

Controller time constant (Ta) (>0). Typical Value = 0. Default: 0.0

tb:

Gate servo time constant (Tb) (>0). Typical Value = 0. Default: 0.0

treg:

Speed detector time constant (Treg). Default: 0.0

tw:

Water inertia time constant (Tw) (>0). Typical Value = 0. Default: 0.0

velmax:

Maximum gate opening velocity (Velmax). Unit = PU/sec. Typical Value = 0. Default: 0.0

velmin:

Maximum gate closing velocity (Velmin). Unit = PU/sec. Typical Value = 0. Default: 0.0

Documentation of parent class TurbineGovernorDynamics:

Turbine-governor function block whose behavior is described by reference to a standard model

AsynchronousMachineDynamics:

Asynchronous machine model with which this turbine-governor model is associated. Default: None

SynchronousMachineDynamics:

Turbine-governor model associated with this synchronous machine model. Default: “list”

TurbineLoadControllerDynamics:

Turbine load controller providing input to this turbine-governor. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled:

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects:

The domain object to which this diagram object is associated. Default: “list”

description:

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic:

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

mRID:

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’