cimpy.cgmes_v2_4_15.ExcST7B module
- class cimpy.cgmes_v2_4_15.ExcST7B.ExcST7B(kh=0.0, kia=0.0, kl=0.0, kpa=0.0, oelin=None, tb=0.0, tc=0.0, tf=0.0, tg=0.0, tia=0.0, ts=0.0, uelin=None, vmax=0.0, vmin=0.0, vrmax=0.0, vrmin=0.0, *args, **kw_args)[source]
Modified IEEE ST7B static excitation system without stator current limiter (SCL) and current compensator (DROOP) inputs.
- kh:
High-value gate feedback gain (Kh). Typical Value = 1. Default: 0.0
- kia:
Voltage regulator integral gain (Kia). Typical Value = 1. Default: 0.0
- kl:
Low-value gate feedback gain (Kl). Typical Value = 1. Default: 0.0
- kpa:
Voltage regulator proportional gain (Kpa). Typical Value = 40. Default: 0.0
- oelin:
OEL input selector (OELin). Typical Value = noOELinput. Default: None
- tb:
Regulator lag time constant (Tb). Typical Value = 1. Default: 0.0
- tc:
Regulator lead time constant (Tc). Typical Value = 1. Default: 0.0
- tf:
Excitation control system stabilizer time constant (Tf). Typical Value = 1. Default: 0.0
- tg:
Feedback time constant of inner loop field voltage regulator (Tg). Typical Value = 1. Default: 0.0
- tia:
Feedback time constant (Tia). Typical Value = 3. Default: 0.0
- ts:
Rectifier firing time constant (Ts). Typical Value = 0. Default: 0.0
- uelin:
UEL input selector (UELin). Typical Value = noUELinput. Default: None
- vmax:
Maximum voltage reference signal (Vmax). Typical Value = 1.1. Default: 0.0
- vmin:
Minimum voltage reference signal (Vmin). Typical Value = 0.9. Default: 0.0
- vrmax:
Maximum voltage regulator output (Vrmax). Typical Value = 5. Default: 0.0
- vrmin:
Minimum voltage regulator output (Vrmin). Typical Value = -4.5. Default: 0.0
Documentation of parent class ExcitationSystemDynamics:
Excitation system function block whose behavior is described by reference to a standard model
- DiscontinuousExcitationControlDynamics:
Discontinuous excitation control model associated with this excitation system model. Default: None
- OverexcitationLimiterDynamics:
Overexcitation limiter model associated with this excitation system model. Default: None
- PFVArControllerType1Dynamics:
Power Factor or VAr controller Type I model associated with this excitation system model. Default: None
- PFVArControllerType2Dynamics:
Power Factor or VAr controller Type II model associated with this excitation system model. Default: None
- PowerSystemStabilizerDynamics:
Power system stabilizer model associated with this excitation system model. Default: None
- SynchronousMachineDynamics:
Synchronous machine model with which this excitation system model is associated. Default: None
- UnderexcitationLimiterDynamics:
Undrexcitation limiter model associated with this excitation system model. Default: None
- VoltageCompensatorDynamics:
Voltage compensator model associated with this excitation system model. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName: