cimpy.cgmes_v2_4_15.GovHydroPelton module
- class cimpy.cgmes_v2_4_15.GovHydroPelton.GovHydroPelton(av0=0.0, av1=0.0, bp=0.0, db1=0.0, db2=0.0, h1=0.0, h2=0.0, hn=0.0, kc=0.0, kg=0.0, qc0=0.0, qn=0.0, simplifiedPelton=False, staticCompensating=False, ta=0.0, ts=0.0, tv=0.0, twnc=0.0, twng=0.0, tx=0.0, va=0.0, valvmax=0.0, valvmin=0.0, vav=0.0, vc=0.0, vcv=0.0, waterTunnelSurgeChamberSimulation=False, zsfc=0.0, *args, **kw_args)[source]
Detailed hydro unit - Pelton model. This model can be used to represent the dynamic related to water tunnel and surge chamber. A schematic of the hydraulic system of detailed hydro unit models, like Francis and Pelton, is located under the GovHydroFrancis class.
- av0:
Area of the surge tank (A). Unit = m. Typical Value = 30. Default: 0.0
- av1:
Area of the compensation tank (A). Unit = m. Typical Value = 700. Default: 0.0
- bp:
Droop (bp). Typical Value = 0.05. Default: 0.0
- db1:
Intentional dead-band width (DB1). Unit = Hz. Typical Value = 0. Default: 0.0
- db2:
Intentional dead-band width of valve opening error (DB2). Unit = Hz. Typical Value = 0.01. Default: 0.0
- h1:
Head of compensation chamber water level with respect to the level of penstock (H). Unit = m. Typical Value = 4. Default: 0.0
- h2:
Head of surge tank water level with respect to the level of penstock (H). Unit = m. Typical Value = 40. Default: 0.0
- hn:
Rated hydraulic head (H). Unit = m. Typical Value = 250. Default: 0.0
- kc:
Penstock loss coefficient (due to friction) (Kc). Typical Value = 0.025. Default: 0.0
- kg:
Water tunnel and surge chamber loss coefficient (due to friction) (Kg). Typical Value = -0.025. Default: 0.0
- qc0:
No-load turbine flow at nominal head (Qc0). Typical Value = 0.05. Default: 0.0
- qn:
Rated flow (Q). Unit = m/s. Typical Value = 40. Default: 0.0
- simplifiedPelton:
Simplified Pelton model simulation (Sflag). true = enable of simplified Pelton model simulation false = enable of complete Pelton model simulation (non linear gain). Typical Value = false. Default: False
- staticCompensating:
Static compensating characteristic (Cflag). true = enable of static compensating characteristic false = inhibit of static compensating characteristic. Typical Value = false. Default: False
- ta:
Derivative gain (accelerometer time constant) (Ta). Typical Value = 3. Default: 0.0
- ts:
Gate servo time constant (Ts). Typical Value = 0.15. Default: 0.0
- tv:
Servomotor integrator time constant (TV). Typical Value = 0.3. Default: 0.0
- twnc:
Water inertia time constant (Twnc). Typical Value = 1. Default: 0.0
- twng:
Water tunnel and surge chamber inertia time constant (Twng). Typical Value = 3. Default: 0.0
- tx:
Electronic integrator time constant (Tx). Typical Value = 0.5. Default: 0.0
- va:
Maximum gate opening velocity (Va). Unit = PU/sec. Typical Value = 0.016. Default: 0.0
- valvmax:
Maximum gate opening (ValvMax). Typical Value = 1. Default: 0.0
- valvmin:
Minimum gate opening (ValvMin). Typical Value = 0. Default: 0.0
- vav:
Maximum servomotor valve opening velocity (Vav). Typical Value = 0.017. Default: 0.0
- vc:
Maximum gate closing velocity (Vc). Unit = PU/sec. Typical Value = -0.016. Default: 0.0
- vcv:
Maximum servomotor valve closing velocity (Vcv). Typical Value = -0.017. Default: 0.0
- waterTunnelSurgeChamberSimulation:
Water tunnel and surge chamber simulation (Tflag). true = enable of water tunnel and surge chamber simulation false = inhibit of water tunnel and surge chamber simulation. Typical Value = false. Default: False
- zsfc:
Head of upper water level with respect to the level of penstock (Zsfc). Unit = m. Typical Value = 25. Default: 0.0
Documentation of parent class TurbineGovernorDynamics:
Turbine-governor function block whose behavior is described by reference to a standard model
- AsynchronousMachineDynamics:
Asynchronous machine model with which this turbine-governor model is associated. Default: None
- SynchronousMachineDynamics:
Turbine-governor model associated with this synchronous machine model. Default: “list”
- TurbineLoadControllerDynamics:
Turbine load controller providing input to this turbine-governor. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’