cimpy.cgmes_v2_4_15.Pss1 module
- class cimpy.cgmes_v2_4_15.Pss1.Pss1(kf=0.0, kpe=0.0, ks=0.0, kw=0.0, pmin=0.0, t10=0.0, t5=0.0, t6=0.0, t7=0.0, t8=0.0, t9=0.0, tpe=0.0, vadat=False, vsmn=0.0, vsmx=0.0, *args, **kw_args)[source]
Italian PSS - three input PSS (speed, frequency, power).
- kf:
Frequency power input gain (K). Typical Value = 5. Default: 0.0
- kpe:
Electric power input gain (K). Typical Value = 0.3. Default: 0.0
- ks:
PSS gain (K). Typical Value = 1. Default: 0.0
- kw:
Shaft speed power input gain (K). Typical Value = 0. Default: 0.0
- pmin:
Minimum power PSS enabling (P). Typical Value = 0.25. Default: 0.0
- t10:
Lead/lag time constant (T). Typical Value = 0. Default: 0.0
- t5:
Washout (T). Typical Value = 3.5. Default: 0.0
- t6:
Filter time constant (T). Typical Value = 0. Default: 0.0
- t7:
Lead/lag time constant (T). Typical Value = 0. Default: 0.0
- t8:
Lead/lag time constant (T). Typical Value = 0. Default: 0.0
- t9:
Lead/lag time constant (T). Typical Value = 0. Default: 0.0
- tpe:
Electric power filter time constant (T). Typical Value = 0.05. Default: 0.0
- vadat:
Default: False
- vsmn:
Stabilizer output max limit (V). Typical Value = -0.06. Default: 0.0
- vsmx:
Stabilizer output min limit (V). Typical Value = 0.06. Default: 0.0
Documentation of parent class PowerSystemStabilizerDynamics:
Power system stabilizer function block whose behaviour is described by reference to a standard model
- ExcitationSystemDynamics:
Excitation system model with which this power system stabilizer model is associated. Default: None
- RemoteInputSignal:
Remote input signal used by this power system stabilizer model. Default: “list”
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’