cimpy.cgmes_v2_4_15.GovHydroPID2 module

class cimpy.cgmes_v2_4_15.GovHydroPID2.GovHydroPID2(atw=0.0, d=0.0, feedbackSignal=False, g0=0.0, g1=0.0, g2=0.0, gmax=0.0, gmin=0.0, kd=0.0, ki=0.0, kp=0.0, mwbase=0.0, p1=0.0, p2=0.0, p3=0.0, rperm=0.0, ta=0.0, tb=0.0, treg=0.0, tw=0.0, velmax=0.0, velmin=0.0, *args, **kw_args)[source]

Hydro turbine and governor. Represents plants with straight forward penstock configurations and “three term” electro-hydraulic governors (i.e. Woodard electronic).

atw:

Factor multiplying Tw (Atw). Typical Value = 0. Default: 0.0

d:

Turbine damping factor (D). Unit = delta P / delta speed. Typical Value = 0. Default: 0.0

feedbackSignal:

Feedback signal type flag (Flag). true = use gate position feedback signal false = use Pe. Default: False

g0:

Gate opening at speed no load (G0). Typical Value = 0. Default: 0.0

g1:

Intermediate gate opening (G1). Typical Value = 0. Default: 0.0

g2:

Intermediate gate opening (G2). Typical Value = 0. Default: 0.0

gmax:

Maximum gate opening (Gmax). Typical Value = 0. Default: 0.0

gmin:

Minimum gate opening (Gmin). Typical Value = 0. Default: 0.0

kd:

Derivative gain (Kd). Typical Value = 0. Default: 0.0

ki:

Reset gain (Ki). Unit = PU/ sec. Typical Value = 0. Default: 0.0

kp:

Proportional gain (Kp). Typical Value = 0. Default: 0.0

mwbase:

Base for power values (MWbase) (>0). Unit = MW. Default: 0.0

p1:

Power at gate opening G1 (P1). Typical Value = 0. Default: 0.0

p2:

Power at gate opening G2 (P2). Typical Value = 0. Default: 0.0

p3:

Power at full opened gate (P3). Typical Value = 0. Default: 0.0

rperm:

Permanent drop (Rperm). Typical Value = 0. Default: 0.0

ta:

Controller time constant (Ta) (>0). Typical Value = 0. Default: 0.0

tb:

Gate servo time constant (Tb) (>0). Typical Value = 0. Default: 0.0

treg:

Speed detector time constant (Treg). Typical Value = 0. Default: 0.0

tw:

Water inertia time constant (Tw) (>0). Typical Value = 0. Default: 0.0

velmax:

Maximum gate opening velocity (Velmax). Unit = PU/sec. Typical Value = 0. Default: 0.0

velmin:

Maximum gate closing velocity (Velmin). Unit = PU/sec. Typical Value = 0. Default: 0.0

Documentation of parent class TurbineGovernorDynamics:

Turbine-governor function block whose behavior is described by reference to a standard model

AsynchronousMachineDynamics:

Asynchronous machine model with which this turbine-governor model is associated. Default: None

SynchronousMachineDynamics:

Turbine-governor model associated with this synchronous machine model. Default: “list”

TurbineLoadControllerDynamics:

Turbine load controller providing input to this turbine-governor. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled:

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects:

The domain object to which this diagram object is associated. Default: “list”

description:

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic:

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

mRID:

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name:

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

shortName:

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.GovHydroPID2