cimpy.cgmes_v2_4_15.GovSteamEU module
- class cimpy.cgmes_v2_4_15.GovSteamEU.GovSteamEU(chc=0.0, cho=0.0, cic=0.0, cio=0.0, db1=0.0, db2=0.0, hhpmax=0.0, ke=0.0, kfcor=0.0, khp=0.0, klp=0.0, kwcor=0.0, mwbase=0.0, pmax=0.0, prhmax=0.0, simx=0.0, tb=0.0, tdp=0.0, ten=0.0, tf=0.0, tfp=0.0, thp=0.0, tip=0.0, tlp=0.0, tp=0.0, trh=0.0, tvhp=0.0, tvip=0.0, tw=0.0, wfmax=0.0, wfmin=0.0, wmax1=0.0, wmax2=0.0, wwmax=0.0, wwmin=0.0, *args, **kw_args)[source]
Simplified model of boiler and steam turbine with PID governor.
- chc:
Control valves rate closing limit (Chc). Unit = PU/sec. Typical Value = -3.3. Default: 0.0
- cho:
Control valves rate opening limit (Cho). Unit = PU/sec. Typical Value = 0.17. Default: 0.0
- cic:
Intercept valves rate closing limit (Cic). Typical Value = -2.2. Default: 0.0
- cio:
Intercept valves rate opening limit (Cio). Typical Value = 0.123. Default: 0.0
- db1:
Dead band of the frequency corrector (db1). Typical Value = 0. Default: 0.0
- db2:
Dead band of the speed governor (db2). Typical Value = 0.0004. Default: 0.0
- hhpmax:
Maximum control valve position (Hhpmax). Typical Value = 1. Default: 0.0
- ke:
Gain of the power controller (Ke). Typical Value = 0.65. Default: 0.0
- kfcor:
Gain of the frequency corrector (Kfcor). Typical Value = 20. Default: 0.0
- khp:
Fraction of total turbine output generated by HP part (Khp). Typical Value = 0.277. Default: 0.0
- klp:
Fraction of total turbine output generated by HP part (Klp). Typical Value = 0.723. Default: 0.0
- kwcor:
Gain of the speed governor (Kwcor). Typical Value = 20. Default: 0.0
- mwbase:
Base for power values (MWbase) (>0). Unit = MW. Default: 0.0
- pmax:
Maximal active power of the turbine (Pmax). Typical Value = 1. Default: 0.0
- prhmax:
Maximum low pressure limit (Prhmax). Typical Value = 1.4. Default: 0.0
- simx:
Intercept valves transfer limit (Simx). Typical Value = 0.425. Default: 0.0
- tb:
Boiler time constant (Tb). Typical Value = 100. Default: 0.0
- tdp:
Derivative time constant of the power controller (Tdp). Typical Value = 0. Default: 0.0
- ten:
Electro hydraulic transducer (Ten). Typical Value = 0.1. Default: 0.0
- tf:
Frequency transducer time constant (Tf). Typical Value = 0. Default: 0.0
- tfp:
Time constant of the power controller (Tfp). Typical Value = 0. Default: 0.0
- thp:
High pressure (HP) time constant of the turbine (Thp). Typical Value = 0.31. Default: 0.0
- tip:
Integral time constant of the power controller (Tip). Typical Value = 2. Default: 0.0
- tlp:
Low pressure(LP) time constant of the turbine (Tlp). Typical Value = 0.45. Default: 0.0
- tp:
Power transducer time constant (Tp). Typical Value = 0.07. Default: 0.0
- trh:
Reheater time constant of the turbine (Trh). Typical Value = 8. Default: 0.0
- tvhp:
Control valves servo time constant (Tvhp). Typical Value = 0.1. Default: 0.0
- tvip:
Intercept valves servo time constant (Tvip). Typical Value = 0.15. Default: 0.0
- tw:
Speed transducer time constant (Tw). Typical Value = 0.02. Default: 0.0
- wfmax:
Upper limit for frequency correction (Wfmax). Typical Value = 0.05. Default: 0.0
- wfmin:
Lower limit for frequency correction (Wfmin). Typical Value = -0.05. Default: 0.0
- wmax1:
Emergency speed control lower limit (wmax1). Typical Value = 1.025. Default: 0.0
- wmax2:
Emergency speed control upper limit (wmax2). Typical Value = 1.05. Default: 0.0
- wwmax:
Upper limit for the speed governor (Wwmax). Typical Value = 0.1. Default: 0.0
- wwmin:
Lower limit for the speed governor frequency correction (Wwmin). Typical Value = -1. Default: 0.0
Documentation of parent class TurbineGovernorDynamics:
Turbine-governor function block whose behavior is described by reference to a standard model
- AsynchronousMachineDynamics:
Asynchronous machine model with which this turbine-governor model is associated. Default: None
- SynchronousMachineDynamics:
Turbine-governor model associated with this synchronous machine model. Default: “list”
- TurbineLoadControllerDynamics:
Turbine load controller providing input to this turbine-governor. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’