cimpy.cgmes_v2_4_15.GovSteamFV4 module
- class cimpy.cgmes_v2_4_15.GovSteamFV4.GovSteamFV4(cpsmn=0.0, cpsmx=0.0, crmn=0.0, crmx=0.0, kdc=0.0, kf1=0.0, kf3=0.0, khp=0.0, kic=0.0, kip=0.0, kit=0.0, kmp1=0.0, kmp2=0.0, kpc=0.0, kpp=0.0, kpt=0.0, krc=0.0, ksh=0.0, lpi=0.0, lps=0.0, mnef=0.0, mxef=0.0, pr1=0.0, pr2=0.0, psmn=0.0, rsmimn=0.0, rsmimx=0.0, rvgmn=0.0, rvgmx=0.0, srmn=0.0, srmx=0.0, srsmp=0.0, svmn=0.0, svmx=0.0, ta=0.0, tam=0.0, tc=0.0, tcm=0.0, tdc=0.0, tf1=0.0, tf2=0.0, thp=0.0, tmp=0.0, trh=0.0, tv=0.0, ty=0.0, y=0.0, yhpmn=0.0, yhpmx=0.0, ympmn=0.0, ympmx=0.0, *args, **kw_args)[source]
Detailed electro-hydraulic governor for steam unit.
- cpsmn:
Minimum value of pressure regulator output (Cpsmn). Typical Value = -1. Default: 0.0
- cpsmx:
Maximum value of pressure regulator output (Cpsmx). Typical Value = 1. Default: 0.0
- crmn:
Minimum value of regulator set-point (Crmn). Typical Value = 0. Default: 0.0
- crmx:
Maximum value of regulator set-point (Crmx). Typical Value = 1.2. Default: 0.0
- kdc:
Derivative gain of pressure regulator (Kdc). Typical Value = 1. Default: 0.0
- kf1:
Frequency bias (reciprocal of droop) (Kf1). Typical Value = 20. Default: 0.0
- kf3:
Frequency control (reciprocal of droop) (Kf3). Typical Value = 20. Default: 0.0
- khp:
Fraction of total turbine output generated by HP part (Khp). Typical Value = 0.35. Default: 0.0
- kic:
Integral gain of pressure regulator (Kic). Typical Value = 0.0033. Default: 0.0
- kip:
Integral gain of pressure feedback regulator (Kip). Typical Value = 0.5. Default: 0.0
- kit:
Integral gain of electro-hydraulic regulator (Kit). Typical Value = 0.04. Default: 0.0
- kmp1:
First gain coefficient of intercept valves characteristic (Kmp1). Typical Value = 0.5. Default: 0.0
- kmp2:
Second gain coefficient of intercept valves characteristic (Kmp2). Typical Value = 3.5. Default: 0.0
- kpc:
Proportional gain of pressure regulator (Kpc). Typical Value = 0.5. Default: 0.0
- kpp:
Proportional gain of pressure feedback regulator (Kpp). Typical Value = 1. Default: 0.0
- kpt:
Proportional gain of electro-hydraulic regulator (Kpt). Typical Value = 0.3. Default: 0.0
- krc:
Maximum variation of fuel flow (Krc). Typical Value = 0.05. Default: 0.0
- ksh:
Pressure loss due to flow friction in the boiler tubes (Ksh). Typical Value = 0.08. Default: 0.0
- lpi:
Maximum negative power error (Lpi). Typical Value = -0.15. Default: 0.0
- lps:
Maximum positive power error (Lps). Typical Value = 0.03. Default: 0.0
- mnef:
Lower limit for frequency correction (MN). Typical Value = -0.05. Default: 0.0
- mxef:
Upper limit for frequency correction (MX). Typical Value = 0.05. Default: 0.0
- pr1:
First value of pressure set point static characteristic (Pr1). Typical Value = 0.2. Default: 0.0
- pr2:
Second value of pressure set point static characteristic, corresponding to Ps0 = 1.0 PU (Pr2). Typical Value = 0.75. Default: 0.0
- psmn:
Minimum value of pressure set point static characteristic (Psmn). Typical Value = 1. Default: 0.0
- rsmimn:
Minimum value of integral regulator (Rsmimn). Typical Value = 0. Default: 0.0
- rsmimx:
Maximum value of integral regulator (Rsmimx). Typical Value = 1.1. Default: 0.0
- rvgmn:
Minimum value of integral regulator (Rvgmn). Typical Value = 0. Default: 0.0
- rvgmx:
Maximum value of integral regulator (Rvgmx). Typical Value = 1.2. Default: 0.0
- srmn:
Minimum valve opening (Srmn). Typical Value = 0. Default: 0.0
- srmx:
Maximum valve opening (Srmx). Typical Value = 1.1. Default: 0.0
- srsmp:
Intercept valves characteristic discontinuity point (Srsmp). Typical Value = 0.43. Default: 0.0
- svmn:
Maximum regulator gate closing velocity (Svmn). Typical Value = -0.0333. Default: 0.0
- svmx:
Maximum regulator gate opening velocity (Svmx). Typical Value = 0.0333. Default: 0.0
- ta:
Control valves rate opening time (Ta). Typical Value = 0.8. Default: 0.0
- tam:
Intercept valves rate opening time (Tam). Typical Value = 0.8. Default: 0.0
- tc:
Control valves rate closing time (Tc). Typical Value = 0.5. Default: 0.0
- tcm:
Intercept valves rate closing time (Tcm). Typical Value = 0.5. Default: 0.0
- tdc:
Derivative time constant of pressure regulator (Tdc). Typical Value = 90. Default: 0.0
- tf1:
Time constant of fuel regulation (Tf1). Typical Value = 10. Default: 0.0
- tf2:
Time constant of steam chest (Tf2). Typical Value = 10. Default: 0.0
- thp:
High pressure (HP) time constant of the turbine (Thp). Typical Value = 0.15. Default: 0.0
- tmp:
Low pressure (LP) time constant of the turbine (Tmp). Typical Value = 0.4. Default: 0.0
- trh:
Reheater time constant of the turbine (Trh). Typical Value = 10. Default: 0.0
- tv:
Boiler time constant (Tv). Typical Value = 60. Default: 0.0
- ty:
Control valves servo time constant (Ty). Typical Value = 0.1. Default: 0.0
- y:
Coefficient of linearized equations of turbine (Stodola formulation) (Y). Typical Value = 0.13. Default: 0.0
- yhpmn:
Minimum control valve position (Yhpmn). Typical Value = 0. Default: 0.0
- yhpmx:
Maximum control valve position (Yhpmx). Typical Value = 1.1. Default: 0.0
- ympmn:
Minimum intercept valve position (Ympmn). Typical Value = 0. Default: 0.0
- ympmx:
Maximum intercept valve position (Ympmx). Typical Value = 1.1. Default: 0.0
Documentation of parent class TurbineGovernorDynamics:
Turbine-governor function block whose behavior is described by reference to a standard model
- AsynchronousMachineDynamics:
Asynchronous machine model with which this turbine-governor model is associated. Default: None
- SynchronousMachineDynamics:
Turbine-governor model associated with this synchronous machine model. Default: “list”
- TurbineLoadControllerDynamics:
Turbine load controller providing input to this turbine-governor. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’