cimpy.cgmes_v2_4_15.GovSteamFV4 module

class cimpy.cgmes_v2_4_15.GovSteamFV4.GovSteamFV4(cpsmn=0.0, cpsmx=0.0, crmn=0.0, crmx=0.0, kdc=0.0, kf1=0.0, kf3=0.0, khp=0.0, kic=0.0, kip=0.0, kit=0.0, kmp1=0.0, kmp2=0.0, kpc=0.0, kpp=0.0, kpt=0.0, krc=0.0, ksh=0.0, lpi=0.0, lps=0.0, mnef=0.0, mxef=0.0, pr1=0.0, pr2=0.0, psmn=0.0, rsmimn=0.0, rsmimx=0.0, rvgmn=0.0, rvgmx=0.0, srmn=0.0, srmx=0.0, srsmp=0.0, svmn=0.0, svmx=0.0, ta=0.0, tam=0.0, tc=0.0, tcm=0.0, tdc=0.0, tf1=0.0, tf2=0.0, thp=0.0, tmp=0.0, trh=0.0, tv=0.0, ty=0.0, y=0.0, yhpmn=0.0, yhpmx=0.0, ympmn=0.0, ympmx=0.0, *args, **kw_args)[source]

Detailed electro-hydraulic governor for steam unit.

cpsmn:

Minimum value of pressure regulator output (Cpsmn). Typical Value = -1. Default: 0.0

cpsmx:

Maximum value of pressure regulator output (Cpsmx). Typical Value = 1. Default: 0.0

crmn:

Minimum value of regulator set-point (Crmn). Typical Value = 0. Default: 0.0

crmx:

Maximum value of regulator set-point (Crmx). Typical Value = 1.2. Default: 0.0

kdc:

Derivative gain of pressure regulator (Kdc). Typical Value = 1. Default: 0.0

kf1:

Frequency bias (reciprocal of droop) (Kf1). Typical Value = 20. Default: 0.0

kf3:

Frequency control (reciprocal of droop) (Kf3). Typical Value = 20. Default: 0.0

khp:

Fraction of total turbine output generated by HP part (Khp). Typical Value = 0.35. Default: 0.0

kic:

Integral gain of pressure regulator (Kic). Typical Value = 0.0033. Default: 0.0

kip:

Integral gain of pressure feedback regulator (Kip). Typical Value = 0.5. Default: 0.0

kit:

Integral gain of electro-hydraulic regulator (Kit). Typical Value = 0.04. Default: 0.0

kmp1:

First gain coefficient of intercept valves characteristic (Kmp1). Typical Value = 0.5. Default: 0.0

kmp2:

Second gain coefficient of intercept valves characteristic (Kmp2). Typical Value = 3.5. Default: 0.0

kpc:

Proportional gain of pressure regulator (Kpc). Typical Value = 0.5. Default: 0.0

kpp:

Proportional gain of pressure feedback regulator (Kpp). Typical Value = 1. Default: 0.0

kpt:

Proportional gain of electro-hydraulic regulator (Kpt). Typical Value = 0.3. Default: 0.0

krc:

Maximum variation of fuel flow (Krc). Typical Value = 0.05. Default: 0.0

ksh:

Pressure loss due to flow friction in the boiler tubes (Ksh). Typical Value = 0.08. Default: 0.0

lpi:

Maximum negative power error (Lpi). Typical Value = -0.15. Default: 0.0

lps:

Maximum positive power error (Lps). Typical Value = 0.03. Default: 0.0

mnef:

Lower limit for frequency correction (MN). Typical Value = -0.05. Default: 0.0

mxef:

Upper limit for frequency correction (MX). Typical Value = 0.05. Default: 0.0

pr1:

First value of pressure set point static characteristic (Pr1). Typical Value = 0.2. Default: 0.0

pr2:

Second value of pressure set point static characteristic, corresponding to Ps0 = 1.0 PU (Pr2). Typical Value = 0.75. Default: 0.0

psmn:

Minimum value of pressure set point static characteristic (Psmn). Typical Value = 1. Default: 0.0

rsmimn:

Minimum value of integral regulator (Rsmimn). Typical Value = 0. Default: 0.0

rsmimx:

Maximum value of integral regulator (Rsmimx). Typical Value = 1.1. Default: 0.0

rvgmn:

Minimum value of integral regulator (Rvgmn). Typical Value = 0. Default: 0.0

rvgmx:

Maximum value of integral regulator (Rvgmx). Typical Value = 1.2. Default: 0.0

srmn:

Minimum valve opening (Srmn). Typical Value = 0. Default: 0.0

srmx:

Maximum valve opening (Srmx). Typical Value = 1.1. Default: 0.0

srsmp:

Intercept valves characteristic discontinuity point (Srsmp). Typical Value = 0.43. Default: 0.0

svmn:

Maximum regulator gate closing velocity (Svmn). Typical Value = -0.0333. Default: 0.0

svmx:

Maximum regulator gate opening velocity (Svmx). Typical Value = 0.0333. Default: 0.0

ta:

Control valves rate opening time (Ta). Typical Value = 0.8. Default: 0.0

tam:

Intercept valves rate opening time (Tam). Typical Value = 0.8. Default: 0.0

tc:

Control valves rate closing time (Tc). Typical Value = 0.5. Default: 0.0

tcm:

Intercept valves rate closing time (Tcm). Typical Value = 0.5. Default: 0.0

tdc:

Derivative time constant of pressure regulator (Tdc). Typical Value = 90. Default: 0.0

tf1:

Time constant of fuel regulation (Tf1). Typical Value = 10. Default: 0.0

tf2:

Time constant of steam chest (Tf2). Typical Value = 10. Default: 0.0

thp:

High pressure (HP) time constant of the turbine (Thp). Typical Value = 0.15. Default: 0.0

tmp:

Low pressure (LP) time constant of the turbine (Tmp). Typical Value = 0.4. Default: 0.0

trh:

Reheater time constant of the turbine (Trh). Typical Value = 10. Default: 0.0

tv:

Boiler time constant (Tv). Typical Value = 60. Default: 0.0

ty:

Control valves servo time constant (Ty). Typical Value = 0.1. Default: 0.0

y:

Coefficient of linearized equations of turbine (Stodola formulation) (Y). Typical Value = 0.13. Default: 0.0

yhpmn:

Minimum control valve position (Yhpmn). Typical Value = 0. Default: 0.0

yhpmx:

Maximum control valve position (Yhpmx). Typical Value = 1.1. Default: 0.0

ympmn:

Minimum intercept valve position (Ympmn). Typical Value = 0. Default: 0.0

ympmx:

Maximum intercept valve position (Ympmx). Typical Value = 1.1. Default: 0.0

Documentation of parent class TurbineGovernorDynamics:

Turbine-governor function block whose behavior is described by reference to a standard model

AsynchronousMachineDynamics:

Asynchronous machine model with which this turbine-governor model is associated. Default: None

SynchronousMachineDynamics:

Turbine-governor model associated with this synchronous machine model. Default: “list”

TurbineLoadControllerDynamics:

Turbine load controller providing input to this turbine-governor. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled:

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects:

The domain object to which this diagram object is associated. Default: “list”

description:

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic:

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

mRID:

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name:

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

shortName:

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.GovSteamFV4