cimpy.cgmes_v2_4_15.GovHydroIEEE2 module
- class cimpy.cgmes_v2_4_15.GovHydroIEEE2.GovHydroIEEE2(aturb=0.0, bturb=0.0, gv1=0.0, gv2=0.0, gv3=0.0, gv4=0.0, gv5=0.0, gv6=0.0, kturb=0.0, mwbase=0.0, pgv1=0.0, pgv2=0.0, pgv3=0.0, pgv4=0.0, pgv5=0.0, pgv6=0.0, pmax=0.0, pmin=0.0, rperm=0.0, rtemp=0.0, tg=0.0, tp=0.0, tr=0.0, tw=0.0, uc=0.0, uo=0.0, *args, **kw_args)[source]
IEEE hydro turbine governor model represents plants with straightforward penstock configurations and hydraulic-dashpot governors. Ref
- aturb:
Turbine numerator multiplier (Aturb). Typical Value = -1. Default: 0.0
- bturb:
Turbine denominator multiplier (Bturb). Typical Value = 0.5. Default: 0.0
- gv1:
Nonlinear gain point 1, PU gv (Gv1). Typical Value = 0. Default: 0.0
- gv2:
Nonlinear gain point 2, PU gv (Gv2). Typical Value = 0. Default: 0.0
- gv3:
Nonlinear gain point 3, PU gv (Gv3). Typical Value = 0. Default: 0.0
- gv4:
Nonlinear gain point 4, PU gv (Gv4). Typical Value = 0. Default: 0.0
- gv5:
Nonlinear gain point 5, PU gv (Gv5). Typical Value = 0. Default: 0.0
- gv6:
Nonlinear gain point 6, PU gv (Gv6). Typical Value = 0. Default: 0.0
- kturb:
Turbine gain (Kturb). Typical Value = 1. Default: 0.0
- mwbase:
Base for power values (MWbase) (> 0). Unit = MW. Default: 0.0
- pgv1:
Nonlinear gain point 1, PU power (Pgv1). Typical Value = 0. Default: 0.0
- pgv2:
Nonlinear gain point 2, PU power (Pgv2). Typical Value = 0. Default: 0.0
- pgv3:
Nonlinear gain point 3, PU power (Pgv3). Typical Value = 0. Default: 0.0
- pgv4:
Nonlinear gain point 4, PU power (Pgv4). Typical Value = 0. Default: 0.0
- pgv5:
Nonlinear gain point 5, PU power (Pgv5). Typical Value = 0. Default: 0.0
- pgv6:
Nonlinear gain point 6, PU power (Pgv6). Typical Value = 0. Default: 0.0
- pmax:
Maximum gate opening (Pmax). Typical Value = 1. Default: 0.0
- pmin:
Minimum gate opening (Pmin). Typical Value = 0. Default: 0.0
- rperm:
Permanent droop (Rperm). Typical Value = 0.05. Default: 0.0
- rtemp:
Temporary droop (Rtemp). Typical Value = 0.5. Default: 0.0
- tg:
Gate servo time constant (Tg). Typical Value = 0.5. Default: 0.0
- tp:
Pilot servo valve time constant (Tp). Typical Value = 0.03. Default: 0.0
- tr:
Dashpot time constant (Tr). Typical Value = 12. Default: 0.0
- tw:
Water inertia time constant (Tw). Typical Value = 2. Default: 0.0
- uc:
Maximum gate closing velocity (Uc) (<0). Typical Value = -0.1. Default: 0.0
- uo:
Maximum gate opening velocity (Uo). Unit = PU/sec. Typical Value = 0.1. Default: 0.0
Documentation of parent class TurbineGovernorDynamics:
Turbine-governor function block whose behavior is described by reference to a standard model
- AsynchronousMachineDynamics:
Asynchronous machine model with which this turbine-governor model is associated. Default: None
- SynchronousMachineDynamics:
Turbine-governor model associated with this synchronous machine model. Default: “list”
- TurbineLoadControllerDynamics:
Turbine load controller providing input to this turbine-governor. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’