cimpy.cgmes_v2_4_15.ExcAC3A module
- class cimpy.cgmes_v2_4_15.ExcAC3A.ExcAC3A(efdn=0.0, ka=0.0, kc=0.0, kd=0.0, ke=0.0, kf=0.0, kf1=0.0, kf2=0.0, klv=0.0, kn=0.0, kr=0.0, ks=0.0, seve1=0.0, seve2=0.0, ta=0.0, tb=0.0, tc=0.0, te=0.0, tf=0.0, vamax=0.0, vamin=0.0, ve1=0.0, ve2=0.0, vemin=0.0, vfemax=0.0, vlv=0.0, *args, **kw_args)[source]
Modified IEEE AC3A alternator-supplied rectifier excitation system with different field current limit.
- efdn:
Value of at which feedback gain changes (Efdn). Typical Value = 2.36. Default: 0.0
- ka:
Voltage regulator gain (Ka). Typical Value = 45.62. Default: 0.0
- kc:
Rectifier loading factor proportional to commutating reactance (Kc). Typical Value = 0.104. Default: 0.0
- kd:
Demagnetizing factor, a function of exciter alternator reactances (Kd). Typical Value = 0.499. Default: 0.0
- ke:
Exciter constant related to self-excited field (Ke). Typical Value = 1. Default: 0.0
- kf:
Excitation control system stabilizer gains (Kf). Typical Value = 0.143. Default: 0.0
- kf1:
Coefficient to allow different usage of the model (Kf1). Typical Value = 1. Default: 0.0
- kf2:
Coefficient to allow different usage of the model (Kf2). Typical Value = 0. Default: 0.0
- klv:
Gain used in the minimum field voltage limiter loop (Klv). Typical Value = 0.194. Default: 0.0
- kn:
Excitation control system stabilizer gain (Kn). Typical Value =0.05. Default: 0.0
- kr:
Constant associated with regulator and alternator field power supply (Kr). Typical Value =3.77. Default: 0.0
- ks:
Coefficient to allow different usage of the model-speed coefficient (Ks). Typical Value = 0. Default: 0.0
- seve1:
Exciter saturation function value at the corresponding exciter voltage, Ve, back of commutating reactance (Se[Ve]). Typical Value = 1.143. Default: 0.0
- seve2:
Exciter saturation function value at the corresponding exciter voltage, Ve, back of commutating reactance (Se[Ve]). Typical Value = 0.1. Default: 0.0
- ta:
Voltage regulator time constant (Ta). Typical Value = 0.013. Default: 0.0
- tb:
Voltage regulator time constant (Tb). Typical Value = 0. Default: 0.0
- tc:
Voltage regulator time constant (T). Typical Value = 0. Default: 0.0
- te:
Exciter time constant, integration rate associated with exciter control (Te). Typical Value = 1.17. Default: 0.0
- tf:
Excitation control system stabilizer time constant (Tf). Typical Value = 1. Default: 0.0
- vamax:
Maximum voltage regulator output (V). Typical Value = 1. Default: 0.0
- vamin:
Minimum voltage regulator output (V). Typical Value = -0.95. Default: 0.0
- ve1:
Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve1) equals Vemax (Ve1). Typical Value = 6.24. Default: 0.0
- ve2:
Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve). Typical Value = 4.68. Default: 0.0
- vemin:
Minimum exciter voltage output (Vemin). Typical Value = 0.1. Default: 0.0
- vfemax:
Exciter field current limit reference (Vfemax). Typical Value = 16. Default: 0.0
- vlv:
Field voltage used in the minimum field voltage limiter loop (Vlv). Typical Value = 0.79. Default: 0.0
Documentation of parent class ExcitationSystemDynamics:
Excitation system function block whose behavior is described by reference to a standard model
- DiscontinuousExcitationControlDynamics:
Discontinuous excitation control model associated with this excitation system model. Default: None
- OverexcitationLimiterDynamics:
Overexcitation limiter model associated with this excitation system model. Default: None
- PFVArControllerType1Dynamics:
Power Factor or VAr controller Type I model associated with this excitation system model. Default: None
- PFVArControllerType2Dynamics:
Power Factor or VAr controller Type II model associated with this excitation system model. Default: None
- PowerSystemStabilizerDynamics:
Power system stabilizer model associated with this excitation system model. Default: None
- SynchronousMachineDynamics:
Synchronous machine model with which this excitation system model is associated. Default: None
- UnderexcitationLimiterDynamics:
Undrexcitation limiter model associated with this excitation system model. Default: None
- VoltageCompensatorDynamics:
Voltage compensator model associated with this excitation system model. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’