cimpy.cgmes_v2_4_15.UnderexcLim2Simplified module
- class cimpy.cgmes_v2_4_15.UnderexcLim2Simplified.UnderexcLim2Simplified(kui=0.0, p0=0.0, p1=0.0, q0=0.0, q1=0.0, vuimax=0.0, vuimin=0.0, *args, **kw_args)[source]
This model can be derived from UnderexcLimIEEE2. The limit characteristic (look -up table) is a single straight-line, the same as UnderexcLimIEEE2 (see Figure 10.4 (p 32), IEEE 421.5-2005 Section 10.2).
- kui:
Gain Under excitation limiter (Kui). Typical Value = 0.1. Default: 0.0
- p0:
Segment P initial point (P0). Typical Value = 0. Default: 0.0
- p1:
Segment P end point (P1). Typical Value = 1. Default: 0.0
- q0:
Segment Q initial point (Q0). Typical Value = -0.31. Default: 0.0
- q1:
Segment Q end point (Q1). Typical Value = -0.1. Default: 0.0
- vuimax:
Maximum error signal (V). Typical Value = 1. Default: 0.0
- vuimin:
Minimum error signal (V). Typical Value = 0. Default: 0.0
Documentation of parent class UnderexcitationLimiterDynamics:
Underexcitation limiter function block whose behaviour is described by reference to a standard model
- ExcitationSystemDynamics:
Excitation system model with which this underexcitation limiter model is associated. Default: None
- RemoteInputSignal:
Remote input signal used by this underexcitation limiter model. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’