cimpy.cgmes_v2_4_15.GovSteamFV2 module
- class cimpy.cgmes_v2_4_15.GovSteamFV2.GovSteamFV2(dt=0.0, k=0.0, mwbase=0.0, r=0.0, t1=0.0, t3=0.0, ta=0.0, tb=0.0, tc=0.0, ti=0.0, tt=0.0, vmax=0.0, vmin=0.0, *args, **kw_args)[source]
Steam turbine governor with reheat time constants and modeling of the effects of fast valve closing to reduce mechanical power.
- dt:
(Dt). Default: 0.0
- k:
Fraction of the turbine power developed by turbine sections not involved in fast valving (K). Default: 0.0
- mwbase:
Alternate Base used instead of Machine base in equipment model if necessary (MWbase) (>0). Unit = MW. Default: 0.0
- r:
(R). Default: 0.0
- t1:
Governor time constant (T1). Default: 0.0
- t3:
Reheater time constant (T3). Default: 0.0
- ta:
Time after initial time for valve to close (Ta). Default: 0.0
- tb:
Time after initial time for valve to begin opening (Tb). Default: 0.0
- tc:
Time after initial time for valve to become fully open (Tc). Default: 0.0
- ti:
Initial time to begin fast valving (Ti). Default: 0.0
- tt:
Time constant with which power falls off after intercept valve closure (Tt). Default: 0.0
- vmax:
(Vmax). Default: 0.0
- vmin:
(Vmin). Default: 0.0
Documentation of parent class TurbineGovernorDynamics:
Turbine-governor function block whose behavior is described by reference to a standard model
- AsynchronousMachineDynamics:
Asynchronous machine model with which this turbine-governor model is associated. Default: None
- SynchronousMachineDynamics:
Turbine-governor model associated with this synchronous machine model. Default: “list”
- TurbineLoadControllerDynamics:
Turbine load controller providing input to this turbine-governor. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’