cimpy.cgmes_v2_4_15.ExcAC6A module

class cimpy.cgmes_v2_4_15.ExcAC6A.ExcAC6A(ka=0.0, kc=0.0, kd=0.0, ke=0.0, kh=0.0, ks=0.0, seve1=0.0, seve2=0.0, ta=0.0, tb=0.0, tc=0.0, te=0.0, th=0.0, tj=0.0, tk=0.0, vamax=0.0, vamin=0.0, ve1=0.0, ve2=0.0, vfelim=0.0, vhmax=0.0, vrmax=0.0, vrmin=0.0, *args, **kw_args)[source]

Modified IEEE AC6A alternator-supplied rectifier excitation system with speed input.

ka:

Voltage regulator gain (Ka). Typical Value = 536. Default: 0.0

kc:

Rectifier loading factor proportional to commutating reactance (Kc). Typical Value = 0.173. Default: 0.0

kd:

Demagnetizing factor, a function of exciter alternator reactances (Kd). Typical Value = 1.91. Default: 0.0

ke:

Exciter constant related to self-excited field (Ke). Typical Value = 1.6. Default: 0.0

kh:

Exciter field current limiter gain (Kh). Typical Value = 92. Default: 0.0

ks:

Coefficient to allow different usage of the model-speed coefficient (Ks). Typical Value = 0. Default: 0.0

seve1:

Exciter saturation function value at the corresponding exciter voltage, Ve1, back of commutating reactance (Se[Ve1]). Typical Value = 0.214. Default: 0.0

seve2:

Exciter saturation function value at the corresponding exciter voltage, Ve2, back of commutating reactance (Se[Ve2]). Typical Value = 0.044. Default: 0.0

ta:

Voltage regulator time constant (Ta). Typical Value = 0.086. Default: 0.0

tb:

Voltage regulator time constant (Tb). Typical Value = 9. Default: 0.0

tc:

Voltage regulator time constant (Tc). Typical Value = 3. Default: 0.0

te:

Exciter time constant, integration rate associated with exciter control (Te). Typical Value = 1. Default: 0.0

th:

Exciter field current limiter time constant (Th). Typical Value = 0.08. Default: 0.0

tj:

Exciter field current limiter time constant (Tj). Typical Value = 0.02. Default: 0.0

tk:

Voltage regulator time constant (Tk). Typical Value = 0.18. Default: 0.0

vamax:

Maximum voltage regulator output (Vamax). Typical Value = 75. Default: 0.0

vamin:

Minimum voltage regulator output (Vamin). Typical Value = -75. Default: 0.0

ve1:

Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve). Typical Value = 7.4. Default: 0.0

ve2:

Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve2). Typical Value = 5.55. Default: 0.0

vfelim:

Exciter field current limit reference (Vfelim). Typical Value = 19. Default: 0.0

vhmax:

Maximum field current limiter signal reference (Vhmax). Typical Value = 75. Default: 0.0

vrmax:

Maximum voltage regulator output (Vrmax). Typical Value = 44. Default: 0.0

vrmin:

Minimum voltage regulator output (Vrmin). Typical Value = -36. Default: 0.0

Documentation of parent class ExcitationSystemDynamics:

Excitation system function block whose behavior is described by reference to a standard model

DiscontinuousExcitationControlDynamics:

Discontinuous excitation control model associated with this excitation system model. Default: None

OverexcitationLimiterDynamics:

Overexcitation limiter model associated with this excitation system model. Default: None

PFVArControllerType1Dynamics:

Power Factor or VAr controller Type I model associated with this excitation system model. Default: None

PFVArControllerType2Dynamics:

Power Factor or VAr controller Type II model associated with this excitation system model. Default: None

PowerSystemStabilizerDynamics:

Power system stabilizer model associated with this excitation system model. Default: None

SynchronousMachineDynamics:

Synchronous machine model with which this excitation system model is associated. Default: None

UnderexcitationLimiterDynamics:

Undrexcitation limiter model associated with this excitation system model. Default: None

VoltageCompensatorDynamics:

Voltage compensator model associated with this excitation system model. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled:

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects:

The domain object to which this diagram object is associated. Default: “list”

description:

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic:

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

mRID:

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name:

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

shortName:

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.ExcAC6A