cimpy.cgmes_v2_4_15.GovGAST module
- class cimpy.cgmes_v2_4_15.GovGAST.GovGAST(at=0.0, dturb=0.0, kt=0.0, mwbase=0.0, r=0.0, t1=0.0, t2=0.0, t3=0.0, vmax=0.0, vmin=0.0, *args, **kw_args)[source]
Single shaft gas turbine.
- at:
Ambient temperature load limit (Load Limit). Typical Value = 1. Default: 0.0
- dturb:
Turbine damping factor (Dturb). Typical Value = 0.18. Default: 0.0
- kt:
Temperature limiter gain (Kt). Typical Value = 3. Default: 0.0
- mwbase:
Base for power values (MWbase) (> 0). Default: 0.0
- r:
Permanent droop (R). Typical Value = 0.04. Default: 0.0
- t1:
Governor mechanism time constant (T1). T1 represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical Value = 0.5. Default: 0.0
- t2:
Turbine power time constant (T2). T2 represents delay due to internal energy storage of the gas turbine engine. T2 can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi-shaft engine, or with the compressibility of gas in the plenum of a the free power turbine of an aero-derivative unit, for example. Typical Value = 0.5. Default: 0.0
- t3:
Turbine exhaust temperature time constant (T3). Typical Value = 3. Default: 0.0
- vmax:
Maximum turbine power, PU of MWbase (Vmax). Typical Value = 1. Default: 0.0
- vmin:
Minimum turbine power, PU of MWbase (Vmin). Typical Value = 0. Default: 0.0
Documentation of parent class TurbineGovernorDynamics:
Turbine-governor function block whose behavior is described by reference to a standard model
- AsynchronousMachineDynamics:
Asynchronous machine model with which this turbine-governor model is associated. Default: None
- SynchronousMachineDynamics:
Turbine-governor model associated with this synchronous machine model. Default: “list”
- TurbineLoadControllerDynamics:
Turbine load controller providing input to this turbine-governor. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’