cimpy.cgmes_v2_4_15.ExcST2A module
- class cimpy.cgmes_v2_4_15.ExcST2A.ExcST2A(efdmax=0.0, ka=0.0, kc=0.0, ke=0.0, kf=0.0, ki=0.0, kp=0.0, ta=0.0, tb=0.0, tc=0.0, te=0.0, tf=0.0, uelin=False, vrmax=0.0, vrmin=0.0, *args, **kw_args)[source]
Modified IEEE ST2A static excitation system - another lead-lag block added to match the model defined by WECC.
- efdmax:
Maximum field voltage (Efdmax). Typical Value = 99. Default: 0.0
- ka:
Voltage regulator gain (Ka). Typical Value = 120. Default: 0.0
- kc:
Rectifier loading factor proportional to commutating reactance (Kc). Typical Value = 1.82. Default: 0.0
- ke:
Exciter constant related to self-excited field (Ke). Typical Value = 1. Default: 0.0
- kf:
Excitation control system stabilizer gains (Kf). Typical Value = 0.05. Default: 0.0
- ki:
Potential circuit gain coefficient (Ki). Typical Value = 8. Default: 0.0
- kp:
Potential circuit gain coefficient (Kp). Typical Value = 4.88. Default: 0.0
- ta:
Voltage regulator time constant (Ta). Typical Value = 0.15. Default: 0.0
- tb:
Voltage regulator time constant (Tb). Typical Value = 0. Default: 0.0
- tc:
Voltage regulator time constant (Tc). Typical Value = 0. Default: 0.0
- te:
Exciter time constant, integration rate associated with exciter control (Te). Typical Value = 0.5. Default: 0.0
- tf:
Excitation control system stabilizer time constant (Tf). Typical Value = 0.7. Default: 0.0
- uelin:
UEL input (UELin). true = HV gate false = add to error signal. Typical Value = false. Default: False
- vrmax:
Maximum voltage regulator outputs (Vrmax). Typical Value = 1. Default: 0.0
- vrmin:
Minimum voltage regulator outputs (Vrmin). Typical Value = -1. Default: 0.0
Documentation of parent class ExcitationSystemDynamics:
Excitation system function block whose behavior is described by reference to a standard model
- DiscontinuousExcitationControlDynamics:
Discontinuous excitation control model associated with this excitation system model. Default: None
- OverexcitationLimiterDynamics:
Overexcitation limiter model associated with this excitation system model. Default: None
- PFVArControllerType1Dynamics:
Power Factor or VAr controller Type I model associated with this excitation system model. Default: None
- PFVArControllerType2Dynamics:
Power Factor or VAr controller Type II model associated with this excitation system model. Default: None
- PowerSystemStabilizerDynamics:
Power system stabilizer model associated with this excitation system model. Default: None
- SynchronousMachineDynamics:
Synchronous machine model with which this excitation system model is associated. Default: None
- UnderexcitationLimiterDynamics:
Undrexcitation limiter model associated with this excitation system model. Default: None
- VoltageCompensatorDynamics:
Voltage compensator model associated with this excitation system model. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’