- class cimpy.cgmes_v2_4_15.ExcST6B.ExcST6B(ilr=0.0, k1=False, kcl=0.0, kff=0.0, kg=0.0, kia=0.0, klr=0.0, km=0.0, kpa=0.0, kvd=0.0, oelin=None, tg=0.0, ts=0.0, tvd=0.0, vamax=0.0, vamin=0.0, vilim=False, vimax=0.0, vimin=0.0, vmult=False, vrmax=0.0, vrmin=0.0, xc=0.0, *args, **kw_args)[source]
Modified IEEE ST6B static excitation system with PID controller and optional inner feedbacks loop.
- ilr:
Exciter output current limit reference (Ilr). Typical Value = 4.164. Default: 0.0
- k1:
Selector (K1). true = feedback is from Ifd false = feedback is not from Ifd. Typical Value = true. Default: False
- kcl:
Exciter output current limit adjustment (Kcl). Typical Value = 1.0577. Default: 0.0
- kff:
Pre-control gain constant of the inner loop field regulator (Kff). Typical Value = 1. Default: 0.0
- kg:
Feedback gain constant of the inner loop field regulator (Kg). Typical Value = 1. Default: 0.0
- kia:
Voltage regulator integral gain (Kia). Typical Value = 45.094. Default: 0.0
- klr:
Exciter output current limit adjustment (Kcl). Typical Value = 17.33. Default: 0.0
- km:
Forward gain constant of the inner loop field regulator (Km). Typical Value = 1. Default: 0.0
- kpa:
Voltage regulator proportional gain (Kpa). Typical Value = 18.038. Default: 0.0
- kvd:
Voltage regulator derivative gain (Kvd). Typical Value = 0. Default: 0.0
- oelin:
OEL input selector (OELin). Typical Value = noOELinput. Default: None
- tg:
Feedback time constant of inner loop field voltage regulator (Tg). Typical Value = 0.02. Default: 0.0
- ts:
Rectifier firing time constant (Ts). Typical Value = 0. Default: 0.0
- tvd:
Voltage regulator derivative gain (Tvd). Typical Value = 0. Default: 0.0
- vamax:
Maximum voltage regulator output (Vamax). Typical Value = 4.81. Default: 0.0
- vamin:
Minimum voltage regulator output (Vamin). Typical Value = -3.85. Default: 0.0
- vilim:
Selector (Vilim). true = Vimin-Vimax limiter is active false = Vimin-Vimax limiter is not active. Typical Value = true. Default: False
- vimax:
Maximum voltage regulator input limit (Vimax). Typical Value = 10. Default: 0.0
- vimin:
Minimum voltage regulator input limit (Vimin). Typical Value = -10. Default: 0.0
- vmult:
Selector (Vmult). true = multiply regulator output by terminal voltage false = do not multiply regulator output by terminal voltage. Typical Value = true. Default: False
- vrmax:
Maximum voltage regulator output (Vrmax). Typical Value = 4.81. Default: 0.0
- vrmin:
Minimum voltage regulator output (Vrmin). Typical Value = -3.85. Default: 0.0
- xc:
Excitation source reactance (Xc). Typical Value = 0.05. Default: 0.0
Documentation of parent class ExcitationSystemDynamics:
Excitation system function block whose behavior is described by reference to a standard model
- DiscontinuousExcitationControlDynamics:
Discontinuous excitation control model associated with this excitation system model. Default: None
- OverexcitationLimiterDynamics:
Overexcitation limiter model associated with this excitation system model. Default: None
- PFVArControllerType1Dynamics:
Power Factor or VAr controller Type I model associated with this excitation system model. Default: None
- PFVArControllerType2Dynamics:
Power Factor or VAr controller Type II model associated with this excitation system model. Default: None
- PowerSystemStabilizerDynamics:
Power system stabilizer model associated with this excitation system model. Default: None
- SynchronousMachineDynamics:
Synchronous machine model with which this excitation system model is associated. Default: None
- UnderexcitationLimiterDynamics:
Undrexcitation limiter model associated with this excitation system model. Default: None
- VoltageCompensatorDynamics:
Voltage compensator model associated with this excitation system model. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’