cimpy.cgmes_v2_4_15.ExcDC3A module
- class cimpy.cgmes_v2_4_15.ExcDC3A.ExcDC3A(edfmax=0.0, efd1=0.0, efd2=0.0, efdlim=False, efdmin=0.0, exclim=False, ke=0.0, kr=0.0, ks=0.0, kv=0.0, seefd1=0.0, seefd2=0.0, te=0.0, trh=0.0, vrmax=0.0, vrmin=0.0, *args, **kw_args)[source]
This is modified IEEE DC3A direct current commutator exciters with speed input, and death band. DC old type 4.
- edfmax:
Maximum voltage exciter output limiter (Efdmax). Typical Value = 99. Default: 0.0
- efd1:
Exciter voltage at which exciter saturation is defined (Efd1). Typical Value = 2.6. Default: 0.0
- efd2:
Exciter voltage at which exciter saturation is defined (Efd2). Typical Value = 3.45. Default: 0.0
- efdlim:
(Efdlim). true = exciter output limiter is active false = exciter output limiter not active. Typical Value = true. Default: False
- efdmin:
Minimum voltage exciter output limiter (Efdmin). Typical Value = -99. Default: 0.0
- exclim:
(exclim). IEEE standard is ambiguous about lower limit on exciter output. true = a lower limit of zero is applied to integrator output false = a lower limit of zero not applied to integrator output. Typical Value = true. Default: False
- ke:
Exciter constant related to self-excited field (Ke). Typical Value = 1. Default: 0.0
- kr:
Death band (Kr). If Kr is not zero, the voltage regulator input changes at a constant rate if Verr > Kr or Verr < -Kr as per the IEEE (1968) Type 4 model. If Kr is zero, the error signal drives the voltage regulator continuously as per the IEEE (1980) DC3 and IEEE (1992, 2005) DC3A models. Typical Value = 0. Default: 0.0
- ks:
Coefficient to allow different usage of the model-speed coefficient (Ks). Typical Value = 0. Default: 0.0
- kv:
Fast raise/lower contact setting (Kv). Typical Value = 0.05. Default: 0.0
- seefd1:
Exciter saturation function value at the corresponding exciter voltage, Efd1 (Se[Eefd1]). Typical Value = 0.1. Default: 0.0
- seefd2:
Exciter saturation function value at the corresponding exciter voltage, Efd2 (Se[Efd2]). Typical Value = 0.35. Default: 0.0
- te:
Exciter time constant, integration rate associated with exciter control (Te). Typical Value = 1.83. Default: 0.0
- trh:
Rheostat travel time (Trh). Typical Value = 20. Default: 0.0
- vrmax:
Maximum voltage regulator output (Vrmax). Typical Value = 5. Default: 0.0
- vrmin:
Minimum voltage regulator output (Vrmin). Typical Value = 0. Default: 0.0
Documentation of parent class ExcitationSystemDynamics:
Excitation system function block whose behavior is described by reference to a standard model
- DiscontinuousExcitationControlDynamics:
Discontinuous excitation control model associated with this excitation system model. Default: None
- OverexcitationLimiterDynamics:
Overexcitation limiter model associated with this excitation system model. Default: None
- PFVArControllerType1Dynamics:
Power Factor or VAr controller Type I model associated with this excitation system model. Default: None
- PFVArControllerType2Dynamics:
Power Factor or VAr controller Type II model associated with this excitation system model. Default: None
- PowerSystemStabilizerDynamics:
Power system stabilizer model associated with this excitation system model. Default: None
- SynchronousMachineDynamics:
Synchronous machine model with which this excitation system model is associated. Default: None
- UnderexcitationLimiterDynamics:
Undrexcitation limiter model associated with this excitation system model. Default: None
- VoltageCompensatorDynamics:
Voltage compensator model associated with this excitation system model. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled:
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects:
The domain object to which this diagram object is associated. Default: “list”
- description:
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic:
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- mRID:
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name:
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- shortName:
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’