cimpy.cgmes_v2_4_15.GovSteamCC module

class cimpy.cgmes_v2_4_15.GovSteamCC.GovSteamCC(dhp=0.0, dlp=0.0, fhp=0.0, flp=0.0, mwbase=0.0, pmaxhp=0.0, pmaxlp=0.0, rhp=0.0, rlp=0.0, t1hp=0.0, t1lp=0.0, t3hp=0.0, t3lp=0.0, t4hp=0.0, t4lp=0.0, t5hp=0.0, t5lp=0.0, *args, **kw_args)[source]

Cross compound turbine governor model.

dhp:

HP damping factor (Dhp). Typical Value = 0. Default: 0.0

dlp:

LP damping factor (Dlp). Typical Value = 0. Default: 0.0

fhp:

Fraction of HP power ahead of reheater (Fhp). Typical Value = 0.3. Default: 0.0

flp:

Fraction of LP power ahead of reheater (Flp). Typical Value = 0.7. Default: 0.0

mwbase:

Base for power values (MWbase) (>0). Unit = MW. Default: 0.0

pmaxhp:

Maximum HP value position (Pmaxhp). Typical Value = 1. Default: 0.0

pmaxlp:

Maximum LP value position (Pmaxlp). Typical Value = 1. Default: 0.0

rhp:

HP governor droop (Rhp). Typical Value = 0.05. Default: 0.0

rlp:

LP governor droop (Rlp). Typical Value = 0.05. Default: 0.0

t1hp:

HP governor time constant (T1hp). Typical Value = 0.1. Default: 0.0

t1lp:

LP governor time constant (T1lp). Typical Value = 0.1. Default: 0.0

t3hp:

HP turbine time constant (T3hp). Typical Value = 0.1. Default: 0.0

t3lp:

LP turbine time constant (T3lp). Typical Value = 0.1. Default: 0.0

t4hp:

HP turbine time constant (T4hp). Typical Value = 0.1. Default: 0.0

t4lp:

LP turbine time constant (T4lp). Typical Value = 0.1. Default: 0.0

t5hp:

HP reheater time constant (T5hp). Typical Value = 10. Default: 0.0

t5lp:

LP reheater time constant (T5lp). Typical Value = 10. Default: 0.0

Documentation of parent class TurbineGovernorDynamics:

Turbine-governor function block whose behavior is described by reference to a standard model

AsynchronousMachineDynamics:

Asynchronous machine model with which this turbine-governor model is associated. Default: None

SynchronousMachineDynamics:

Turbine-governor model associated with this synchronous machine model. Default: “list”

TurbineLoadControllerDynamics:

Turbine load controller providing input to this turbine-governor. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled:

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects:

The domain object to which this diagram object is associated. Default: “list”

description:

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic:

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

mRID:

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name:

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

shortName:

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.GovSteamCC