cimpy.cgmes_v2_4_15.GovHydro2 module

class cimpy.cgmes_v2_4_15.GovHydro2.GovHydro2(aturb=0.0, bturb=0.0, db1=0.0, db2=0.0, eps=0.0, gv1=0.0, gv2=0.0, gv3=0.0, gv4=0.0, gv5=0.0, gv6=0.0, kturb=0.0, mwbase=0.0, pgv1=0.0, pgv2=0.0, pgv3=0.0, pgv4=0.0, pgv5=0.0, pgv6=0.0, pmax=0.0, pmin=0.0, rperm=0.0, rtemp=0.0, tg=0.0, tp=0.0, tr=0.0, tw=0.0, uc=0.0, uo=0.0, *args, **kw_args)[source]

IEEE hydro turbine governor model represents plants with straightforward penstock configurations and hydraulic-dashpot governors.

aturb:

Turbine numerator multiplier (Aturb). Typical Value = -1. Default: 0.0

bturb:

Turbine denominator multiplier (Bturb). Typical Value = 0.5. Default: 0.0

db1:

Intentional deadband width (db1). Unit = Hz. Typical Value = 0. Default: 0.0

db2:

Unintentional deadband (db2). Unit = MW. Typical Value = 0. Default: 0.0

eps:

Intentional db hysteresis (eps). Unit = Hz. Typical Value = 0. Default: 0.0

gv1:

Nonlinear gain point 1, PU gv (Gv1). Typical Value = 0. Default: 0.0

gv2:

Nonlinear gain point 2, PU gv (Gv2). Typical Value = 0. Default: 0.0

gv3:

Nonlinear gain point 3, PU gv (Gv3). Typical Value = 0. Default: 0.0

gv4:

Nonlinear gain point 4, PU gv (Gv4). Typical Value = 0. Default: 0.0

gv5:

Nonlinear gain point 5, PU gv (Gv5). Typical Value = 0. Default: 0.0

gv6:

Nonlinear gain point 6, PU gv (Gv6). Typical Value = 0. Default: 0.0

kturb:

Turbine gain (Kturb). Typical Value = 1. Default: 0.0

mwbase:

Base for power values (MWbase) (> 0). Unit = MW. Default: 0.0

pgv1:

Nonlinear gain point 1, PU power (Pgv1). Typical Value = 0. Default: 0.0

pgv2:

Nonlinear gain point 2, PU power (Pgv2). Typical Value = 0. Default: 0.0

pgv3:

Nonlinear gain point 3, PU power (Pgv3). Typical Value = 0. Default: 0.0

pgv4:

Nonlinear gain point 4, PU power (Pgv4). Typical Value = 0. Default: 0.0

pgv5:

Nonlinear gain point 5, PU power (Pgv5). Typical Value = 0. Default: 0.0

pgv6:

Nonlinear gain point 6, PU power (Pgv6). Typical Value = 0. Default: 0.0

pmax:

Maximum gate opening (Pmax). Typical Value = 1. Default: 0.0

pmin:

Minimum gate opening; (). Typical Value = 0. Default: 0.0

rperm:

Permanent droop (Rperm). Typical Value = 0.05. Default: 0.0

rtemp:

Temporary droop (Rtemp). Typical Value = 0.5. Default: 0.0

tg:

Gate servo time constant (Tg). Typical Value = 0.5. Default: 0.0

tp:

Pilot servo valve time constant (Tp). Typical Value = 0.03. Default: 0.0

tr:

Dashpot time constant (Tr). Typical Value = 12. Default: 0.0

tw:

Water inertia time constant (Tw). Typical Value = 2. Default: 0.0

uc:

Maximum gate closing velocity (Uc) (<0). Unit = PU/sec. Typical Value = -0.1. Default: 0.0

uo:

Maximum gate opening velocity (Uo). Unit = PU/sec. Typical Value = 0.1. Default: 0.0

Documentation of parent class TurbineGovernorDynamics:

Turbine-governor function block whose behavior is described by reference to a standard model

AsynchronousMachineDynamics:

Asynchronous machine model with which this turbine-governor model is associated. Default: None

SynchronousMachineDynamics:

Turbine-governor model associated with this synchronous machine model. Default: “list”

TurbineLoadControllerDynamics:

Turbine load controller providing input to this turbine-governor. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled:

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects:

The domain object to which this diagram object is associated. Default: “list”

description:

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic:

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

mRID:

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name:

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

shortName:

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.GovHydro2