cimpy.cgmes_v2_4_15.ExcIEEEDC1A module

class cimpy.cgmes_v2_4_15.ExcIEEEDC1A.ExcIEEEDC1A(efd1=0.0, efd2=0.0, exclim=False, ka=0.0, ke=0.0, kf=0.0, seefd1=0.0, seefd2=0.0, ta=0.0, tb=0.0, tc=0.0, te=0.0, tf=0.0, uelin=False, vrmax=0.0, vrmin=0.0, *args, **kw_args)[source]

The class represents IEEE Std 421.5-2005 type DC1A model. This model represents field-controlled dc commutator exciters with continuously acting voltage regulators (especially the direct-acting rheostatic, rotating amplifier, and magnetic amplifier types). Because this model has been widely implemented by the industry, it is sometimes used to represent other types of systems when detailed data for them are not available or when a simplified model is required. Reference: IEEE Standard 421.5-2005 Section 5.1.

efd1:

Exciter voltage at which exciter saturation is defined (E). Typical Value = 3.1. Default: 0.0

efd2:

Exciter voltage at which exciter saturation is defined (E). Typical Value = 2.3. Default: 0.0

exclim:

(exclim). IEEE standard is ambiguous about lower limit on exciter output. true = a lower limit of zero is applied to integrator output false = a lower limit of zero is not applied to integrator output. Typical Value = true. Default: False

ka:

Voltage regulator gain (K). Typical Value = 46. Default: 0.0

ke:

Exciter constant related to self-excited field (K). Typical Value = 0. Default: 0.0

kf:

Excitation control system stabilizer gain (K). Typical Value = 0.1. Default: 0.0

seefd1:

Exciter saturation function value at the corresponding exciter voltage, E (S[E]). Typical Value = 0.33. Default: 0.0

seefd2:

Exciter saturation function value at the corresponding exciter voltage, E (S[E]). Typical Value = 0.1. Default: 0.0

ta:

Voltage regulator time constant (T). Typical Value = 0.06. Default: 0.0

tb:

Voltage regulator time constant (T). Typical Value = 0. Default: 0.0

tc:

Voltage regulator time constant (T). Typical Value = 0. Default: 0.0

te:

Exciter time constant, integration rate associated with exciter control (T). Typical Value = 0.46. Default: 0.0

tf:

Excitation control system stabilizer time constant (T). Typical Value = 1. Default: 0.0

uelin:

UEL input (uelin). true = input is connected to the HV gate false = input connects to the error signal. Typical Value = true. Default: False

vrmax:

Maximum voltage regulator output (V). Typical Value = 1. Default: 0.0

vrmin:

Minimum voltage regulator output (V). Typical Value = -0.9. Default: 0.0

Documentation of parent class ExcitationSystemDynamics:

Excitation system function block whose behavior is described by reference to a standard model

DiscontinuousExcitationControlDynamics:

Discontinuous excitation control model associated with this excitation system model. Default: None

OverexcitationLimiterDynamics:

Overexcitation limiter model associated with this excitation system model. Default: None

PFVArControllerType1Dynamics:

Power Factor or VAr controller Type I model associated with this excitation system model. Default: None

PFVArControllerType2Dynamics:

Power Factor or VAr controller Type II model associated with this excitation system model. Default: None

PowerSystemStabilizerDynamics:

Power system stabilizer model associated with this excitation system model. Default: None

SynchronousMachineDynamics:

Synchronous machine model with which this excitation system model is associated. Default: None

UnderexcitationLimiterDynamics:

Undrexcitation limiter model associated with this excitation system model. Default: None

VoltageCompensatorDynamics:

Voltage compensator model associated with this excitation system model. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled:

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects:

The domain object to which this diagram object is associated. Default: “list”

description:

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic:

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

mRID:

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name:

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

shortName:

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.ExcIEEEDC1A