cimpy.cgmes_v2_4_15.SynchronousMachineTimeConstantReactance module

class cimpy.cgmes_v2_4_15.SynchronousMachineTimeConstantReactance.SynchronousMachineTimeConstantReactance(rotorType=None, modelType=None, ks=0.0, xDirectSync=0.0, xDirectTrans=0.0, xDirectSubtrans=0.0, xQuadSync=0.0, xQuadTrans=0.0, xQuadSubtrans=0.0, tpdo=0, tppdo=0, tpqo=0, tppqo=0, tc=0, *args, **kw_args)[source]

Synchronous machine detailed modelling types are defined by the combination of the attributes SynchronousMachineTimeConstantReactance.modelType and SynchronousMachineTimeConstantReactance.rotorType. The parameters used for models expressed in time constant reactance form include:

rotorType

Type of rotor on physical machine. Default: None

modelType

Type of synchronous machine model used in Dynamic simulation applications. Default: None

ks

Saturation loading correction factor (Ks) (>= 0). Used only by Type J model. Typical Value = 0. Default: 0.0

xDirectSync

Direct-axis synchronous reactance (Xd) (>= X`d). The quotient of a sustained value of that AC component of armature voltage that is produced by the total direct-axis flux due to direct-axis armature current and the value of the AC component of this current, the machine running at rated speed. Typical Value = 1.8. Default: 0.0

xDirectTrans

Direct-axis transient reactance (unsaturated) (X`d) (> =X``d). Typical Value = 0.5. Default: 0.0

xDirectSubtrans

Direct-axis subtransient reactance (unsaturated) (X``d) (> Xl). Typical Value = 0.2. Default: 0.0

xQuadSync

Quadrature-axis synchronous reactance (Xq) (> =X`q). The ratio of the component of reactive armature voltage, due to the quadrature-axis component of armature current, to this component of current, under steady state conditions and at rated frequency. Typical Value = 1.6. Default: 0.0

xQuadTrans

Quadrature-axis transient reactance (X`q) (> =X``q). Typical Value = 0.3. Default: 0.0

xQuadSubtrans

Quadrature-axis subtransient reactance (X``q) (> Xl). Typical Value = 0.2. Default: 0.0

tpdo

Direct-axis transient rotor time constant (T`do) (> T``do). Typical Value = 5. Default: 0

tppdo

Direct-axis subtransient rotor time constant (T``do) (> 0). Typical Value = 0.03. Default: 0

tpqo

Quadrature-axis transient rotor time constant (T`qo) (> T``qo). Typical Value = 0.5. Default: 0

tppqo

Quadrature-axis subtransient rotor time constant (T``qo) (> 0). Typical Value = 0.03. Default: 0

tc

Damping time constant for Canay reactance. Typical Value = 0. Default: 0

Documentation of parent class SynchronousMachineDetailed:

All synchronous machine detailed types use a subset of the same data parameters and input/output variables. The several variations differ in the following ways: It is not necessary for each simulation tool to have separate models for each of the model types. The same model can often be used for several types by alternative logic within the model. Also, differences in saturation representation may not result in significant model performance differences so model substitutions are often acceptable.

saturationFactorQAxis

Q-axis saturation factor at rated terminal voltage (S1q) (>= 0). Typical Value = 0.02. Default: 0.0

saturationFactor120QAxis

Q-axis saturation factor at 120% of rated terminal voltage (S12q) (>=S1q). Typical Value = 0.12. Default: 0.0

efdBaseRatio

Ratio of Efd bases of exciter and generator models. Typical Value = 1. Default: 0.0

ifdBaseType

Excitation base system mode. Typical Value = ifag. Default: None

ifdBaseValue

Ifd base current if .ifdBaseType = other. Not needed if .ifdBaseType not = other. Unit = A. Typical Value = 0. Default: 0.0

Documentation of parent class SynchronousMachineDynamics:

Synchronous machine whose behaviour is described by reference to a standard model expressed in one of the following forms:

SynchronousMachine

Synchronous machine to which synchronous machine dynamics model applies. Default: None

TurbineGovernorDynamics

Synchronous machine model with which this turbine-governor model is associated. Default: “list”

ExcitationSystemDynamics

Excitation system model associated with this synchronous machine model. Default: None

MechanicalLoadDynamics

Mechanical load model associated with this synchronous machine model. Default: None

GenICompensationForGenJ

Compensation of voltage compensator`s generator for current flow out of this generator. Default: “list”

Documentation of parent class RotatingMachineDynamics:

Abstract parent class for all synchronous and asynchronous machine standard models.

damping

Damping torque coefficient (D). A proportionality constant that, when multiplied by the angular velocity of the rotor poles with respect to the magnetic field (frequency), results in the damping torque. This value is often zero when the sources of damping torques (generator damper windings, load damping effects, etc.) are modelled in detail. Typical Value = 0. Default: 0.0

inertia

Inertia constant of generator or motor and mechanical load (H) (>0). This is the specification for the stored energy in the rotating mass when operating at rated speed. For a generator, this includes the generator plus all other elements (turbine, exciter) on the same shaft and has units of MW*sec. For a motor, it includes the motor plus its mechanical load. Conventional units are per unit on the generator MVA base, usually expressed as MW*second/MVA or just second. This value is used in the accelerating power reference frame for operator training simulator solutions. Typical Value = 3. Default: 0

saturationFactor

Saturation factor at rated terminal voltage (S1) (> or =0). Not used by simplified model. Defined by defined by S(E1) in the SynchronousMachineSaturationParameters diagram. Typical Value = 0.02. Default: 0.0

saturationFactor120

Saturation factor at 120% of rated terminal voltage (S12) (> or =S1). Not used by the simplified model, defined by S(E2) in the SynchronousMachineSaturationParameters diagram. Typical Value = 0.12. Default: 0.0

statorLeakageReactance

Stator leakage reactance (Xl) (> or =0). Typical Value = 0.15. Default: 0.0

statorResistance

Stator (armature) resistance (Rs) (> or =0). Typical Value = 0.005. Default: 0.0

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects

The domain object to which this diagram object is associated. Default: “list”

mRID

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

shortName

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

cgmesProfile

alias of Profile

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.SynchronousMachineTimeConstantReactance