cimpy.cgmes_v2_4_15.GovSteam0 module
- class cimpy.cgmes_v2_4_15.GovSteam0.GovSteam0(mwbase=0.0, r=0.0, t1=0, vmax=0.0, vmin=0.0, t2=0, t3=0, dt=0.0, *args, **kw_args)[source]
A simplified steam turbine governor model.
- mwbase
Base for power values (MWbase) (>0). Unit = MW. Default: 0.0
- r
Permanent droop (R). Typical Value = 0.05. Default: 0.0
- t1
Steam bowl time constant (T1). Typical Value = 0.5. Default: 0
- vmax
Maximum valve position, PU of mwcap (Vmax). Typical Value = 1. Default: 0.0
- vmin
Minimum valve position, PU of mwcap (Vmin). Typical Value = 0. Default: 0.0
- t2
Numerator time constant of T2/T3 block (T2). Typical Value = 3. Default: 0
- t3
Reheater time constant (T3). Typical Value = 10. Default: 0
- dt
Turbine damping coefficient (Dt). Unit = delta P / delta speed. Typical Value = 0. Default: 0.0
Documentation of parent class TurbineGovernorDynamics:
Turbine-governor function block whose behavior is described by reference to a standard model
- SynchronousMachineDynamics
Turbine-governor model associated with this synchronous machine model. Default: “list”
- AsynchronousMachineDynamics
Asynchronous machine model with which this turbine-governor model is associated. Default: None
- TurbineLoadControllerDynamics
Turbine load controller providing input to this turbine-governor. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects
The domain object to which this diagram object is associated. Default: “list”
- mRID
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- shortName
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’