cimpy.cgmes_v2_4_15.Pss2B module
- class cimpy.cgmes_v2_4_15.Pss2B.Pss2B(inputSignal1Type=None, inputSignal2Type=None, vsi1max=0.0, vsi1min=0.0, tw1=0, tw2=0, vsi2max=0.0, vsi2min=0.0, tw3=0, tw4=0, t1=0, t2=0, t3=0, t4=0, t6=0, t7=0, t8=0, t9=0, t10=0, t11=0, ks1=0.0, ks2=0.0, ks3=0.0, ks4=0.0, n=0, m=0, vstmax=0.0, vstmin=0.0, a=0.0, ta=0, tb=0, *args, **kw_args)[source]
Modified IEEE PSS2B Model. Extra lead/lag (or rate) block added at end (up to 4 lead/lags total).
- inputSignal1Type
Type of input signal #1. Typical Value = rotorSpeed. Default: None
- inputSignal2Type
Type of input signal #2. Typical Value = generatorElectricalPower. Default: None
- vsi1max
Input signal #1 max limit (Vsi1max). Typical Value = 2. Default: 0.0
- vsi1min
Input signal #1 min limit (Vsi1min). Typical Value = -2. Default: 0.0
- tw1
First washout on signal #1 (Tw1). Typical Value = 2. Default: 0
- tw2
Second washout on signal #1 (Tw2). Typical Value = 2. Default: 0
- vsi2max
Input signal #2 max limit (Vsi2max). Typical Value = 2. Default: 0.0
- vsi2min
Input signal #2 min limit (Vsi2min). Typical Value = -2. Default: 0.0
- tw3
First washout on signal #2 (Tw3). Typical Value = 2. Default: 0
- tw4
Second washout on signal #2 (Tw4). Typical Value = 0. Default: 0
- t1
Lead/lag time constant (T1). Typical Value = 0.12. Default: 0
- t2
Lead/lag time constant (T2). Typical Value = 0.02. Default: 0
- t3
Lead/lag time constant (T3). Typical Value = 0.3. Default: 0
- t4
Lead/lag time constant (T4). Typical Value = 0.02. Default: 0
- t6
Time constant on signal #1 (T6). Typical Value = 0. Default: 0
- t7
Time constant on signal #2 (T7). Typical Value = 2. Default: 0
- t8
Lead of ramp tracking filter (T8). Typical Value = 0.2. Default: 0
- t9
Lag of ramp tracking filter (T9). Typical Value = 0.1. Default: 0
- t10
Lead/lag time constant (T10). Typical Value = 0. Default: 0
- t11
Lead/lag time constant (T11). Typical Value = 0. Default: 0
- ks1
Stabilizer gain (Ks1). Typical Value = 12. Default: 0.0
- ks2
Gain on signal #2 (Ks2). Typical Value = 0.2. Default: 0.0
- ks3
Gain on signal #2 input before ramp-tracking filter (Ks3). Typical Value = 1. Default: 0.0
- ks4
Gain on signal #2 input after ramp-tracking filter (Ks4). Typical Value = 1. Default: 0.0
- n
Order of ramp tracking filter (N). Typical Value = 1. Default: 0
- m
Denominator order of ramp tracking filter (M). Typical Value = 5. Default: 0
- vstmax
Stabilizer output max limit (Vstmax). Typical Value = 0.1. Default: 0.0
- vstmin
Stabilizer output min limit (Vstmin). Typical Value = -0.1. Default: 0.0
- a
Numerator constant (a). Typical Value = 1. Default: 0.0
- ta
Lead constant (Ta). Typical Value = 0. Default: 0
- tb
Lag time constant (Tb). Typical Value = 0. Default: 0
Documentation of parent class PowerSystemStabilizerDynamics:
Power system stabilizer function block whose behaviour is described by reference to a standard model
- RemoteInputSignal
Remote input signal used by this power system stabilizer model. Default: “list”
- ExcitationSystemDynamics
Excitation system model with which this power system stabilizer model is associated. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects
The domain object to which this diagram object is associated. Default: “list”
- mRID
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- shortName
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’