cimpy.cgmes_v2_4_15.GovSteamIEEE1 module

class cimpy.cgmes_v2_4_15.GovSteamIEEE1.GovSteamIEEE1(mwbase=0.0, k=0.0, t1=0, t2=0, t3=0, uo=0.0, uc=0.0, pmax=0.0, pmin=0.0, t4=0, k1=0.0, k2=0.0, t5=0, k3=0.0, k4=0.0, t6=0, k5=0.0, k6=0.0, t7=0, k7=0.0, k8=0.0, *args, **kw_args)[source]

IEEE steam turbine governor model. Ref

mwbase

Base for power values (MWbase) (> 0) Default: 0.0

k

Governor gain (reciprocal of droop) (K) (> 0). Typical Value = 25. Default: 0.0

t1

Governor lag time constant (T1). Typical Value = 0. Default: 0

t2

Governor lead time constant (T2). Typical Value = 0. Default: 0

t3

Valve positioner time constant (T3) (> 0). Typical Value = 0.1. Default: 0

uo

Maximum valve opening velocity (Uo) (> 0). Unit = PU/sec. Typical Value = 1. Default: 0.0

uc

Maximum valve closing velocity (Uc) (< 0). Unit = PU/sec. Typical Value = -10. Default: 0.0

pmax

Maximum valve opening (Pmax) (> Pmin). Typical Value = 1. Default: 0.0

pmin

Minimum valve opening (Pmin) (>= 0). Typical Value = 0. Default: 0.0

t4

Inlet piping/steam bowl time constant (T4). Typical Value = 0.3. Default: 0

k1

Fraction of HP shaft power after first boiler pass (K1). Typical Value = 0.2. Default: 0.0

k2

Fraction of LP shaft power after first boiler pass (K2). Typical Value = 0. Default: 0.0

t5

Time constant of second boiler pass (T5). Typical Value = 5. Default: 0

k3

Fraction of HP shaft power after second boiler pass (K3). Typical Value = 0.3. Default: 0.0

k4

Fraction of LP shaft power after second boiler pass (K4). Typical Value = 0. Default: 0.0

t6

Time constant of third boiler pass (T6). Typical Value = 0.5. Default: 0

k5

Fraction of HP shaft power after third boiler pass (K5). Typical Value = 0.5. Default: 0.0

k6

Fraction of LP shaft power after third boiler pass (K6). Typical Value = 0. Default: 0.0

t7

Time constant of fourth boiler pass (T7). Typical Value = 0. Default: 0

k7

Fraction of HP shaft power after fourth boiler pass (K7). Typical Value = 0. Default: 0.0

k8

Fraction of LP shaft power after fourth boiler pass (K8). Typical Value = 0. Default: 0.0

Documentation of parent class TurbineGovernorDynamics:

Turbine-governor function block whose behavior is described by reference to a standard model

SynchronousMachineDynamics

Turbine-governor model associated with this synchronous machine model. Default: “list”

AsynchronousMachineDynamics

Asynchronous machine model with which this turbine-governor model is associated. Default: None

TurbineLoadControllerDynamics

Turbine load controller providing input to this turbine-governor. Default: None

Documentation of parent class DynamicsFunctionBlock:

Abstract parent class for all Dynamics function blocks.

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False

Documentation of parent class IdentifiedObject:

This is a root class to provide common identification for all classes needing identification and naming attributes.

DiagramObjects

The domain object to which this diagram object is associated. Default: “list”

mRID

Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’

name

The name is any free human readable and possibly non unique text naming the object. Default: ‘’

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’

energyIdentCodeEic

The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’

shortName

The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’

cgmesProfile

alias of Profile

Inheritance Diagram:

Inheritance diagram of cimpy.cgmes_v2_4_15.GovSteamIEEE1