cimpy.cgmes_v2_4_15.GovSteamIEEE1 module
- class cimpy.cgmes_v2_4_15.GovSteamIEEE1.GovSteamIEEE1(mwbase=0.0, k=0.0, t1=0, t2=0, t3=0, uo=0.0, uc=0.0, pmax=0.0, pmin=0.0, t4=0, k1=0.0, k2=0.0, t5=0, k3=0.0, k4=0.0, t6=0, k5=0.0, k6=0.0, t7=0, k7=0.0, k8=0.0, *args, **kw_args)[source]
IEEE steam turbine governor model. Ref
- mwbase
Base for power values (MWbase) (> 0) Default: 0.0
- k
Governor gain (reciprocal of droop) (K) (> 0). Typical Value = 25. Default: 0.0
- t1
Governor lag time constant (T1). Typical Value = 0. Default: 0
- t2
Governor lead time constant (T2). Typical Value = 0. Default: 0
- t3
Valve positioner time constant (T3) (> 0). Typical Value = 0.1. Default: 0
- uo
Maximum valve opening velocity (Uo) (> 0). Unit = PU/sec. Typical Value = 1. Default: 0.0
- uc
Maximum valve closing velocity (Uc) (< 0). Unit = PU/sec. Typical Value = -10. Default: 0.0
- pmax
Maximum valve opening (Pmax) (> Pmin). Typical Value = 1. Default: 0.0
- pmin
Minimum valve opening (Pmin) (>= 0). Typical Value = 0. Default: 0.0
- t4
Inlet piping/steam bowl time constant (T4). Typical Value = 0.3. Default: 0
- k1
Fraction of HP shaft power after first boiler pass (K1). Typical Value = 0.2. Default: 0.0
- k2
Fraction of LP shaft power after first boiler pass (K2). Typical Value = 0. Default: 0.0
- t5
Time constant of second boiler pass (T5). Typical Value = 5. Default: 0
- k3
Fraction of HP shaft power after second boiler pass (K3). Typical Value = 0.3. Default: 0.0
- k4
Fraction of LP shaft power after second boiler pass (K4). Typical Value = 0. Default: 0.0
- t6
Time constant of third boiler pass (T6). Typical Value = 0.5. Default: 0
- k5
Fraction of HP shaft power after third boiler pass (K5). Typical Value = 0.5. Default: 0.0
- k6
Fraction of LP shaft power after third boiler pass (K6). Typical Value = 0. Default: 0.0
- t7
Time constant of fourth boiler pass (T7). Typical Value = 0. Default: 0
- k7
Fraction of HP shaft power after fourth boiler pass (K7). Typical Value = 0. Default: 0.0
- k8
Fraction of LP shaft power after fourth boiler pass (K8). Typical Value = 0. Default: 0.0
Documentation of parent class TurbineGovernorDynamics:
Turbine-governor function block whose behavior is described by reference to a standard model
- SynchronousMachineDynamics
Turbine-governor model associated with this synchronous machine model. Default: “list”
- AsynchronousMachineDynamics
Asynchronous machine model with which this turbine-governor model is associated. Default: None
- TurbineLoadControllerDynamics
Turbine load controller providing input to this turbine-governor. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects
The domain object to which this diagram object is associated. Default: “list”
- mRID
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- shortName
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’