cimpy.cgmes_v2_4_15.ExcIEEEAC6A module
- class cimpy.cgmes_v2_4_15.ExcIEEEAC6A.ExcIEEEAC6A(ka=0.0, ta=0, tk=0, tb=0, tc=0, vamax=0.0, vamin=0.0, vrmax=0.0, vrmin=0.0, te=0, kh=0.0, tj=0, th=0, vfelim=0.0, vhmax=0.0, kc=0.0, kd=0.0, ke=0.0, ve1=0.0, seve1=0.0, ve2=0.0, seve2=0.0, *args, **kw_args)[source]
The class represents IEEE Std 421.5-2005 type AC6A model. The model represents field-controlled alternator-rectifier excitation systems with system-supplied electronic voltage regulators. The maximum output of the regulator, , is a function of terminal voltage, . The field current limiter included in the original model AC6A remains in the 2005 update. Reference: IEEE Standard 421.5-2005 Section 6.6.
- ka
Voltage regulator gain (K). Typical Value = 536. Default: 0.0
- ta
Voltage regulator time constant (T). Typical Value = 0.086. Default: 0
- tk
Voltage regulator time constant (T). Typical Value = 0.18. Default: 0
- tb
Voltage regulator time constant (T). Typical Value = 9. Default: 0
- tc
Voltage regulator time constant (T). Typical Value = 3. Default: 0
- vamax
Maximum voltage regulator output (V). Typical Value = 75. Default: 0.0
- vamin
Minimum voltage regulator output (V). Typical Value = -75. Default: 0.0
- vrmax
Maximum voltage regulator output (V). Typical Value = 44. Default: 0.0
- vrmin
Minimum voltage regulator output (V). Typical Value = -36. Default: 0.0
- te
Exciter time constant, integration rate associated with exciter control (T). Typical Value = 1. Default: 0
- kh
Exciter field current limiter gain (K). Typical Value = 92. Default: 0.0
- tj
Exciter field current limiter time constant (T). Typical Value = 0.02. Default: 0
- th
Exciter field current limiter time constant (T). Typical Value = 0.08. Default: 0
- vfelim
Exciter field current limit reference (V). Typical Value = 19. Default: 0.0
- vhmax
Maximum field current limiter signal reference (V). Typical Value = 75. Default: 0.0
- kc
Rectifier loading factor proportional to commutating reactance (K). Typical Value = 0.173. Default: 0.0
- kd
Demagnetizing factor, a function of exciter alternator reactances (K). Typical Value = 1.91. Default: 0.0
- ke
Exciter constant related to self-excited field (K). Typical Value = 1.6. Default: 0.0
- ve1
Exciter alternator output voltages back of commutating reactance at which saturation is defined (V) equals V(V). Typical Value = 7.4. Default: 0.0
- seve1
Exciter saturation function value at the corresponding exciter voltage, V, back of commutating reactance (S[V]). Typical Value = 0.214. Default: 0.0
- ve2
Exciter alternator output voltages back of commutating reactance at which saturation is defined (V). Typical Value = 5.55. Default: 0.0
- seve2
Exciter saturation function value at the corresponding exciter voltage, V, back of commutating reactance (S[V]). Typical Value = 0.044. Default: 0.0
Documentation of parent class ExcitationSystemDynamics:
Excitation system function block whose behavior is described by reference to a standard model
- SynchronousMachineDynamics
Synchronous machine model with which this excitation system model is associated. Default: None
- PowerSystemStabilizerDynamics
Power system stabilizer model associated with this excitation system model. Default: None
- PFVArControllerType1Dynamics
Power Factor or VAr controller Type I model associated with this excitation system model. Default: None
- VoltageCompensatorDynamics
Voltage compensator model associated with this excitation system model. Default: None
- DiscontinuousExcitationControlDynamics
Discontinuous excitation control model associated with this excitation system model. Default: None
- UnderexcitationLimiterDynamics
Undrexcitation limiter model associated with this excitation system model. Default: None
- PFVArControllerType2Dynamics
Power Factor or VAr controller Type II model associated with this excitation system model. Default: None
- OverexcitationLimiterDynamics
Overexcitation limiter model associated with this excitation system model. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects
The domain object to which this diagram object is associated. Default: “list”
- mRID
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- shortName
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’