cimpy.cgmes_v2_4_15.GovSteamFV3 module
- class cimpy.cgmes_v2_4_15.GovSteamFV3.GovSteamFV3(mwbase=0.0, k=0.0, t1=0, t2=0, t3=0, uo=0.0, uc=0.0, pmax=0.0, pmin=0.0, t4=0, k1=0.0, t5=0, k2=0.0, t6=0, k3=0.0, ta=0, tb=0, tc=0, prmax=0.0, *args, **kw_args)[source]
Simplified GovSteamIEEE1 Steam turbine governor model with Prmax limit and fast valving.
- mwbase
Base for power values (MWbase) (>0). Unit = MW. Default: 0.0
- k
Governor gain, (reciprocal of droop) (K). Typical Value = 20. Default: 0.0
- t1
Governor lead time constant (T1). Typical Value = 0. Default: 0
- t2
Governor lag time constant (T2). Typical Value = 0. Default: 0
- t3
Valve positioner time constant (T3). Typical Value = 0. Default: 0
- uo
Maximum valve opening velocity (Uo). Unit = PU/sec. Typical Value = 0.1. Default: 0.0
- uc
Maximum valve closing velocity (Uc). Unit = PU/sec. Typical Value = -1. Default: 0.0
- pmax
Maximum valve opening, PU of MWbase (Pmax). Typical Value = 1. Default: 0.0
- pmin
Minimum valve opening, PU of MWbase (Pmin). Typical Value = 0. Default: 0.0
- t4
Inlet piping/steam bowl time constant (T4). Typical Value = 0.2. Default: 0
- k1
Fraction of turbine power developed after first boiler pass (K1). Typical Value = 0.2. Default: 0.0
- t5
Time constant of second boiler pass (i.e. reheater) (T5). Typical Value = 0.5. Default: 0
- k2
Fraction of turbine power developed after second boiler pass (K2). Typical Value = 0.2. Default: 0.0
- t6
Time constant of crossover or third boiler pass (T6). Typical Value = 10. Default: 0
- k3
Fraction of hp turbine power developed after crossover or third boiler pass (K3). Typical Value = 0.6. Default: 0.0
- ta
Time to close intercept valve (IV) (Ta). Typical Value = 0.97. Default: 0
- tb
Time until IV starts to reopen (Tb). Typical Value = 0.98. Default: 0
- tc
Time until IV is fully open (Tc). Typical Value = 0.99. Default: 0
- prmax
Max. pressure in reheater (Prmax). Typical Value = 1. Default: 0.0
Documentation of parent class TurbineGovernorDynamics:
Turbine-governor function block whose behavior is described by reference to a standard model
- SynchronousMachineDynamics
Turbine-governor model associated with this synchronous machine model. Default: “list”
- AsynchronousMachineDynamics
Asynchronous machine model with which this turbine-governor model is associated. Default: None
- TurbineLoadControllerDynamics
Turbine load controller providing input to this turbine-governor. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects
The domain object to which this diagram object is associated. Default: “list”
- mRID
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- shortName
The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: ‘’