cimpy.cgmes_v2_4_15.Pss5 module
- class cimpy.cgmes_v2_4_15.Pss5.Pss5(kpe=0.0, kf=0.0, isfreq=False, kpss=0.0, ctw2=False, tw1=0, tw2=0, tl1=0, tl2=0, tl3=0, tl4=0, vsmn=0.0, vsmx=0.0, tpe=0, pmm=0.0, deadband=0.0, vadat=False, *args, **kw_args)[source]
Italian PSS - Detailed PSS.
- kpe
Electric power input gain (K). Typical Value = 0.3. Default: 0.0
- kf
Frequency/shaft speed input gain (K). Typical Value = 5. Default: 0.0
- isfreq
Selector for Frequency/shaft speed input (IsFreq). true = speed false = frequency. Typical Value = true. Default: False
- kpss
PSS gain (K). Typical Value = 1. Default: 0.0
- ctw2
Selector for Second washout enabling (C). true = second washout filter is bypassed false = second washout filter in use. Typical Value = true. Default: False
- tw1
First WashOut (T). Typical Value = 3.5. Default: 0
- tw2
Second WashOut (T). Typical Value = 0. Default: 0
- tl1
Lead/lag time constant (T). Typical Value = 0. Default: 0
- tl2
Lead/lag time constant (T). Typical Value = 0. Default: 0
- tl3
Lead/lag time constant (T). Typical Value = 0. Default: 0
- tl4
Lead/lag time constant (T). Typical Value = 0. Default: 0
- vsmn
Stabilizer output max limit (V). Typical Value = -0.1. Default: 0.0
- vsmx
Stabilizer output min limit (V). Typical Value = 0.1. Default: 0.0
- tpe
Electric power filter time constant (T). Typical Value = 0.05. Default: 0
- pmm
Minimum power PSS enabling (P). Typical Value = 0.25. Default: 0.0
- deadband
Stabilizer output dead band (DeadBand). Typical Value = 0. Default: 0.0
- vadat
Default: False
Documentation of parent class PowerSystemStabilizerDynamics:
Power system stabilizer function block whose behaviour is described by reference to a standard model
- RemoteInputSignal
Remote input signal used by this power system stabilizer model. Default: “list”
- ExcitationSystemDynamics
Excitation system model with which this power system stabilizer model is associated. Default: None
Documentation of parent class DynamicsFunctionBlock:
Abstract parent class for all Dynamics function blocks.
- enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: False
Documentation of parent class IdentifiedObject:
This is a root class to provide common identification for all classes needing identification and naming attributes.
- DiagramObjects
The domain object to which this diagram object is associated. Default: “list”
- mRID
Master resource identifier issued by a model authority. The mRID is globally unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552 Edition 1, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: ‘’
- name
The name is any free human readable and possibly non unique text naming the object. Default: ‘’
- description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: ‘’
- energyIdentCodeEic
The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. References: Default: ‘’
- shortName