An electromechanical device that operates with shaft rotating synchronously with the network. It is a single machine operating either as a generator or synchronous condenser or pump.
More...
|
|
static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const BaseClassDefiner | declare () |
|
static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const BaseClassDefiner | declare () |
|
static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const BaseClassDefiner | declare () |
|
static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const BaseClassDefiner | declare () |
|
static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const BaseClassDefiner | declare () |
|
static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const BaseClassDefiner | declare () |
|
static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const BaseClassDefiner | declare () |
|
static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const BaseClassDefiner | declare () |
|
static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const CIMPP::BaseClassDefiner | declare () |
|
|
CIMPP::ReactiveCapabilityCurve * | InitialReactiveCapabilityCurve |
| | The default reactive capability curve for use by a synchronous machine. Default: nullptr.
|
|
CIMPP::SynchronousMachineDynamics * | SynchronousMachineDynamics |
| | Synchronous machine dynamics model used to describe dynamic behaviour of this synchronous machine. Default: nullptr.
|
|
CIMPP::Boolean | earthing |
| | Indicates whether or not the generator is earthed. Used for short circuit data exchange according to IEC 60909. Default: false.
|
|
CIMPP::Resistance | earthingStarPointR |
| | Generator star point earthing resistance (Re). Used for short circuit data exchange according to IEC 60909. Default: 0.0.
|
|
CIMPP::Reactance | earthingStarPointX |
| | Generator star point earthing reactance (Xe). Used for short circuit data exchange according to IEC 60909. Default: 0.0.
|
|
CIMPP::CurrentFlow | ikk |
| | Steady-state short-circuit current (in A for the profile) of generator with compound excitation during 3-phase short circuit. - Ikk=0: Generator with no compound excitation. - Ikk<>0: Generator with compound excitation. Ikk is used to calculate the minimum steady-state short-circuit current for generators with compound excitation. (4.6.1.2 in IEC 60909-0:2001). Used only for single fed short circuit on a generator. (4.3.4.2. in IEC 60909-0:2001). Default: 0.0.
|
|
CIMPP::ReactivePower | maxQ |
| | Maximum reactive power limit. This is the maximum (nameplate) limit for the unit. Default: 0.0.
|
|
CIMPP::ReactivePower | minQ |
| | Minimum reactive power limit for the unit. Default: 0.0.
|
|
CIMPP::Float | mu |
| | Factor to calculate the breaking current (Section 4.5.2.1 in IEC 60909-0). Used only for single fed short circuit on a generator (Section 4.3.4.2. in IEC 60909-0). Default: 0.0.
|
|
CIMPP::SynchronousMachineOperatingMode | operatingMode |
| | Current mode of operation. Default: 0.
|
|
CIMPP::PerCent | qPercent |
| | Part of the coordinated reactive control that comes from this machine. The attribute is used as a participation factor not necessarily summing up to 100% for the participating devices in the control. Default: 0.0.
|
|
CIMPP::Resistance | r |
| | Equivalent resistance (RG) of generator. RG is considered for the calculation of all currents, except for the calculation of the peak current ip. Used for short circuit data exchange according to IEC 60909. Default: 0.0.
|
|
CIMPP::Resistance | r0 |
| | Zero sequence resistance of the synchronous machine. Default: 0.0.
|
|
CIMPP::Resistance | r2 |
| | Negative sequence resistance. Default: 0.0.
|
|
CIMPP::Integer | referencePriority |
| | Priority of unit for use as powerflow voltage phase angle reference bus selection. 0 = don t care (default) 1 = highest priority. 2 is less than 1 and so on. Default: 0.
|
| CIMPP::PU | satDirectSyncX |
| | Direct-axis subtransient reactance saturated, also known as Xd`sat. Default: 0.0 */ CIMPP::PU satDirectSubtransX;.
|
|
CIMPP::PU | satDirectTransX |
| | Saturated Direct-axis transient reactance. The attribute is primarily used for short circuit calculations according to ANSI. Default: 0.0.
|
|
CIMPP::ShortCircuitRotorKind | shortCircuitRotorType |
| | Type of rotor, used by short circuit applications, only for single fed short circuit according to IEC 60909. Default: 0.
|
|
CIMPP::SynchronousMachineKind | type |
| | Modes that this synchronous machine can operate in. Default: 0.
|
|
CIMPP::PerCent | voltageRegulationRange |
| | Range of generator voltage regulation (PG in IEC 60909-0) used for calculation of the impedance correction factor KG defined in IEC 60909-0. This attribute is used to describe the operating voltage of the generating unit. Default: 0.0.
|
|
CIMPP::Reactance | x0 |
| | Zero sequence reactance of the synchronous machine. Default: 0.0.
|
|
CIMPP::Reactance | x2 |
| | Negative sequence reactance. Default: 0.0.
|
|
CIMPP::GeneratingUnit * | GeneratingUnit |
| | A synchronous machine may operate as a generator and as such becomes a member of a generating unit. Default: nullptr.
|
|
CIMPP::HydroPump * | HydroPump |
| | The synchronous machine drives the turbine which moves the water from a low elevation to a higher elevation. The direction of machine rotation for pumping may or may not be the same as for generating. Default: nullptr.
|
|
CIMPP::ActivePower | p |
| | Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution. Default: 0.0.
|
|
CIMPP::ReactivePower | q |
| | Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution. Default: 0.0.
|
|
CIMPP::Float | ratedPowerFactor |
| | Power factor (nameplate data). It is primarily used for short circuit data exchange according to IEC 60909. The attribute cannot be a negative value. Default: 0.0.
|
|
CIMPP::ApparentPower | ratedS |
| | Nameplate apparent power rating for the unit. The attribute shall have a positive value. Default: 0.0.
|
|
CIMPP::Voltage | ratedU |
| | Rated voltage (nameplate data, Ur in IEC 60909-0). It is primarily used for short circuit data exchange according to IEC 60909. The attribute shall be a positive value. Default: 0.0.
|
|
CIMPP::RegulatingControl * | RegulatingControl |
| | The regulating control scheme in which this equipment participates. Default: nullptr.
|
|
CIMPP::Boolean | controlEnabled |
| | Specifies the regulation status of the equipment. True is regulating, false is not regulating. Default: false.
|
|
CIMPP::BaseVoltage * | BaseVoltage |
| | Base voltage of this conducting equipment. Use only when there is no voltage level container used and only one base voltage applies. For example, not used for transformers. Default: nullptr.
|
|
CIMPP::SvStatus * | SvStatus |
| | The status state variable associated with this conducting equipment. Default: nullptr.
|
|
std::list< CIMPP::Terminal * > | Terminals |
| | Conducting equipment have terminals that may be connected to other conducting equipment terminals via connectivity nodes or topological nodes. Default: {}.
|
|
CIMPP::EquipmentContainer * | EquipmentContainer |
| | Container of this equipment. Default: nullptr.
|
|
std::list< CIMPP::OperationalLimitSet * > | OperationalLimitSet |
| | The operational limit sets associated with this equipment. Default: {}.
|
|
CIMPP::Boolean | aggregate |
| | The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to true the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine. The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection. Default: false.
|
|
CIMPP::Boolean | inService |
| | Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model. Default: false.
|
|
CIMPP::Boolean | normallyInService |
| | Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model. Default: false.
|
|
std::list< CIMPP::Control * > | Controls |
| | The controller outputs used to actually govern a regulating device, e.g. the magnetization of a synchronous machine or capacitor bank breaker actuator. Default: {}.
|
|
CIMPP::Location * | Location |
| | Location of this power system resource. Default: nullptr.
|
|
std::list< CIMPP::Measurement * > | Measurements |
| | The measurements associated with this power system resource. Default: {}.
|
|
std::list< CIMPP::DiagramObject * > | DiagramObjects |
| | The diagram objects that are associated with the domain object. Default: {}.
|
|
CIMPP::String | description |
| | The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: "".
|
|
CIMPP::String | energyIdentCodeEic |
| | The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. For details on EIC scheme please refer to ENTSO-E web site. Default: "".
|
|
CIMPP::String | mRID |
| | Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: "".
|
|
CIMPP::String | name |
| | The name is any free human readable and possibly non unique text naming the object. Default: "".
|
|
CIMPP::String | shortName |
| | The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: "".
|
An electromechanical device that operates with shaft rotating synchronously with the network. It is a single machine operating either as a generator or synchronous condenser or pump.