static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const BaseClassDefiner | declare () |
|
static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const BaseClassDefiner | declare () |
|
static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const BaseClassDefiner | declare () |
|
static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const BaseClassDefiner | declare () |
|
static void | addConstructToMap (std::unordered_map< std::string, BaseClass *(*)()> &factory_map) |
|
static void | addPrimitiveAssignFnsToMap (std::unordered_map< std::string, assign_function > &assign_map) |
|
static void | addClassAssignFnsToMap (std::unordered_map< std::string, class_assign_function > &assign_map) |
|
static const CIMPP::BaseClassDefiner | declare () |
|
|
CIMPP::Float | chc |
| | Control valves rate closing limit (Chc). Unit = PU / s. Typical value = -3,3. Default: 0.0.
|
|
CIMPP::Float | cho |
| | Control valves rate opening limit (Cho). Unit = PU / s. Typical value = 0,17. Default: 0.0.
|
|
CIMPP::PU | cic |
| | Intercept valves rate closing limit (Cic). Typical value = -2,2. Default: 0.0.
|
|
CIMPP::PU | cio |
| | Intercept valves rate opening limit (Cio). Typical value = 0,123. Default: 0.0.
|
|
CIMPP::PU | db1 |
| | Deadband of the frequency corrector (db1). Typical value = 0. Default: 0.0.
|
|
CIMPP::PU | db2 |
| | Deadband of the speed governor (db2). Typical value = 0,0004. Default: 0.0.
|
|
CIMPP::PU | hhpmax |
| | Maximum control valve position (Hhpmax). Typical value = 1. Default: 0.0.
|
|
CIMPP::PU | ke |
| | Gain of the power controller (Ke). Typical value = 0,65. Default: 0.0.
|
|
CIMPP::PU | kfcor |
| | Gain of the frequency corrector (Kfcor). Typical value = 20. Default: 0.0.
|
|
CIMPP::PU | khp |
| | Fraction of total turbine output generated by HP part (Khp). Typical value = 0,277. Default: 0.0.
|
|
CIMPP::PU | klp |
| | Fraction of total turbine output generated by HP part (Klp). Typical value = 0,723. Default: 0.0.
|
|
CIMPP::PU | komegacor |
| | Gain of the speed governor (Kwcor). Typical value = 20. Default: 0.0.
|
|
CIMPP::ActivePower | mwbase |
| | Base for power values (MWbase) (> 0). Unit = MW. Default: 0.0.
|
|
CIMPP::PU | pmax |
| | Maximal active power of the turbine (Pmax). Typical value = 1. Default: 0.0.
|
|
CIMPP::PU | prhmax |
| | Maximum low pressure limit (Prhmax). Typical value = 1,4. Default: 0.0.
|
|
CIMPP::PU | simx |
| | Intercept valves transfer limit (Simx). Typical value = 0,425. Default: 0.0.
|
|
CIMPP::Seconds | tb |
| | Boiler time constant (Tb) (>= 0). Typical value = 100. Default: 0.0.
|
|
CIMPP::Seconds | tdp |
| | Derivative time constant of the power controller (Tdp) (>= 0). Typical value = 0. Default: 0.0.
|
|
CIMPP::Seconds | ten |
| | Electro hydraulic transducer (Ten) (>= 0). Typical value = 0,1. Default: 0.0.
|
|
CIMPP::Seconds | tf |
| | Frequency transducer time constant (Tf) (>= 0). Typical value = 0. Default: 0.0.
|
|
CIMPP::Seconds | tfp |
| | Time constant of the power controller (Tfp) (>= 0). Typical value = 0. Default: 0.0.
|
|
CIMPP::Seconds | thp |
| | High pressure (HP) time constant of the turbine (Thp) (>= 0). Typical value = 0,31. Default: 0.0.
|
|
CIMPP::Seconds | tip |
| | Integral time constant of the power controller (Tip) (>= 0). Typical value = 2. Default: 0.0.
|
|
CIMPP::Seconds | tlp |
| | Low pressure (LP) time constant of the turbine (Tlp) (>= 0). Typical value = 0,45. Default: 0.0.
|
|
CIMPP::Seconds | tp |
| | Power transducer time constant (Tp) (>= 0). Typical value = 0,07. Default: 0.0.
|
|
CIMPP::Seconds | trh |
| | Reheater time constant of the turbine (Trh) (>= 0). Typical value = 8. Default: 0.0.
|
|
CIMPP::Seconds | tvhp |
| | Control valves servo time constant (Tvhp) (>= 0). Typical value = 0,1. Default: 0.0.
|
|
CIMPP::Seconds | tvip |
| | Intercept valves servo time constant (Tvip) (>= 0). Typical value = 0,15. Default: 0.0.
|
|
CIMPP::Seconds | tw |
| | Speed transducer time constant (Tw) (>= 0). Typical value = 0,02. Default: 0.0.
|
|
CIMPP::PU | wfmax |
| | Upper limit for frequency correction (Wfmax) (> GovSteamEU.wfmin). Typical value = 0,05. Default: 0.0.
|
|
CIMPP::PU | wfmin |
| | Lower limit for frequency correction (Wfmin) (< GovSteamEU.wfmax). Typical value = -0,05. Default: 0.0.
|
|
CIMPP::PU | wmax1 |
| | Emergency speed control lower limit (wmax1). Typical value = 1,025. Default: 0.0.
|
|
CIMPP::PU | wmax2 |
| | Emergency speed control upper limit (wmax2). Typical value = 1,05. Default: 0.0.
|
|
CIMPP::PU | wwmax |
| | Upper limit for the speed governor (Wwmax) (> GovSteamEU.wwmin). Typical value = 0,1. Default: 0.0.
|
|
CIMPP::PU | wwmin |
| | Lower limit for the speed governor frequency correction (Wwmin) (< GovSteamEU.wwmax). Typical value = -1. Default: 0.0.
|
|
CIMPP::AsynchronousMachineDynamics * | AsynchronousMachineDynamics |
| | Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. Default: nullptr.
|
|
CIMPP::SynchronousMachineDynamics * | SynchronousMachineDynamics |
| | Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. Default: nullptr.
|
|
CIMPP::TurbineLoadControllerDynamics * | TurbineLoadControllerDynamics |
| | Turbine load controller providing input to this turbine-governor. Default: nullptr.
|
|
CIMPP::Boolean | enabled |
| | Function block used indicator. true = use of function block is enabled false = use of function block is disabled. Default: false.
|
|
std::list< CIMPP::DiagramObject * > | DiagramObjects |
| | The diagram objects that are associated with the domain object. Default: {}.
|
|
CIMPP::String | description |
| | The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. Default: "".
|
|
CIMPP::String | energyIdentCodeEic |
| | The attribute is used for an exchange of the EIC code (Energy identification Code). The length of the string is 16 characters as defined by the EIC code. For details on EIC scheme please refer to ENTSO-E web site. Default: "".
|
|
CIMPP::String | mRID |
| | Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. Default: "".
|
|
CIMPP::String | name |
| | The name is any free human readable and possibly non unique text naming the object. Default: "".
|
|
CIMPP::String | shortName |
| | The attribute is used for an exchange of a human readable short name with length of the string 12 characters maximum. Default: "".
|
Simplified boiler and steam turbine with PID governor.