10#include <unordered_map>
12#include "TurbineGovernorDynamics.hpp"
13#include "BaseClassDefiner.hpp"
14#include "CGMESProfile.hpp"
15#include "CimClassDetails.hpp"
17#include "ActivePower.hpp"
26 class GovSteamIEEE1 :
public TurbineGovernorDynamics
31 ~GovSteamIEEE1()
override;
96 static const char debugName[];
97 const char* debugString()
const override;
99 const std::list<std::string>& getAttributeNames()
const override;
101 const std::string& getClassNamespaceUrl()
const override;
102 const std::string& getAttributeNamespaceUrl(
const std::string& attrName)
const override;
104 const std::list<CGMESProfile>& getPossibleProfiles()
const override;
105 const CGMESProfile& getRecommendedProfile()
const override;
106 const std::list<CGMESProfile>& getPossibleAttributeProfiles(
const std::string& attrName)
const override;
107 const std::list<CGMESProfile>& getPossibleProfilesIncludingAttributes()
const override;
109 static void addConstructToMap(std::unordered_map<std::string,
BaseClass* (*)()>& factory_map);
110 static void addPrimitiveAssignFnsToMap(std::unordered_map<std::string, assign_function>& assign_map);
111 static void addClassAssignFnsToMap(std::unordered_map<std::string, class_assign_function>& assign_map);
112 void addPrimitiveGetFnsToMap(std::map<std::string, get_function>& get_map)
const override;
113 void addClassGetFnsToMap(std::map<std::string, class_get_function>& get_map)
const override;
114 void addEnumGetFnsToMap(std::map<std::string, get_function>& get_map)
const override;
116 bool isAssignableFrom(
BaseClass* otherObject)
const override;
120 std::map<std::string, AttrDetails> allAttrDetailsMap()
const override;
Definition BaseClass.hpp:22
Product of RMS value of the voltage and the RMS value of the in-phase component of the current.
Definition ActivePower.hpp:14
Definition BaseClassDefiner.hpp:12
A floating point number. The range is unspecified and not limited.
Definition Float.hpp:14
CIMPP::Seconds t3
Valve positioner time constant (T3) (> 0). Typical value = 0,1. Default: 0.0.
Definition GovSteamIEEE1.hpp:76
CIMPP::Float k7
Fraction of HP shaft power after fourth boiler pass (K7). Typical value = 0. Default: 0....
Definition GovSteamIEEE1.hpp:55
CIMPP::Float k8
Fraction of LP shaft power after fourth boiler pass (K8). Typical value = 0. Default: 0....
Definition GovSteamIEEE1.hpp:58
CIMPP::PU k
Governor gain (reciprocal of droop) (K) (> 0). Typical value = 25. Default: 0.0.
Definition GovSteamIEEE1.hpp:34
CIMPP::PU pmax
Maximum valve opening (Pmax) (> GovSteamIEEE1.pmin). Typical value = 1. Default: 0....
Definition GovSteamIEEE1.hpp:64
CIMPP::Float k3
Fraction of HP shaft power after second boiler pass (K3). Typical value = 0,3. Default: 0....
Definition GovSteamIEEE1.hpp:43
CIMPP::Float uo
Maximum valve opening velocity (Uo) (> 0). Unit = PU / s. Typical value = 1. Default: 0....
Definition GovSteamIEEE1.hpp:94
CIMPP::Seconds t2
Governor lead time constant (T2) (>= 0). Typical value = 0. Default: 0.0.
Definition GovSteamIEEE1.hpp:73
CIMPP::Seconds t6
Time constant of third boiler pass (T6) (>= 0). Typical value = 0,5. Default: 0.0.
Definition GovSteamIEEE1.hpp:85
CIMPP::Seconds t5
Time constant of second boiler pass (T5) (>= 0). Typical value = 5. Default: 0.0.
Definition GovSteamIEEE1.hpp:82
CIMPP::Float k4
Fraction of LP shaft power after second boiler pass (K4). Typical value = 0. Default: 0....
Definition GovSteamIEEE1.hpp:46
CIMPP::Float uc
Maximum valve closing velocity (Uc) (< 0). Unit = PU / s. Typical value = -10. Default: 0....
Definition GovSteamIEEE1.hpp:91
CIMPP::ActivePower mwbase
Base for power values (MWbase) (> 0). Unit = MW. Default: 0.0.
Definition GovSteamIEEE1.hpp:61
CIMPP::PU pmin
Minimum valve opening (Pmin) (>= 0 and < GovSteamIEEE1.pmax). Typical value = 0. Default: 0....
Definition GovSteamIEEE1.hpp:67
CIMPP::Seconds t1
Governor lag time constant (T1) (>= 0). Typical value = 0. Default: 0.0.
Definition GovSteamIEEE1.hpp:70
CIMPP::Float k2
Fraction of LP shaft power after first boiler pass (K2). Typical value = 0. Default: 0....
Definition GovSteamIEEE1.hpp:40
CIMPP::Seconds t7
Time constant of fourth boiler pass (T7) (>= 0). Typical value = 0. Default: 0.0.
Definition GovSteamIEEE1.hpp:88
CIMPP::Seconds t4
Inlet piping/steam bowl time constant (T4) (>= 0). Typical value = 0,3. Default: 0....
Definition GovSteamIEEE1.hpp:79
CIMPP::Float k5
Fraction of HP shaft power after third boiler pass (K5). Typical value = 0,5. Default: 0....
Definition GovSteamIEEE1.hpp:49
CIMPP::Float k6
Fraction of LP shaft power after third boiler pass (K6). Typical value = 0. Default: 0....
Definition GovSteamIEEE1.hpp:52
CIMPP::Float k1
Fraction of HP shaft power after first boiler pass (K1). Typical value = 0,2. Default: 0....
Definition GovSteamIEEE1.hpp:37
Per Unit - a positive or negative value referred to a defined base. Values typically range from -10 t...
Definition PU.hpp:14
Time, in seconds.
Definition Seconds.hpp:14